2) Connect the cable to the outdoor unit

1.

Remove the control cover from the unit by loos-

 

ening the screw.

 

Connect the wires to the terminals on the control

 

board individually.

2.

Secure the cable onto the control board with the

 

cord clamp.

3.

Refix the control cover to the original position

 

with the screw.

Outdoor unit

 

Terminal block

 

(Pillar terminal)

 

Connecting

 

cable

Over

Holder for

connecting

5mm

cable

 

 

Cover control

4. Use a recognized circuit breaker "A"

between the power source and the unit.

A disconnecting device to adequately disconnect

all supply lines must be fitted.

Circuit

 

 

Grade

 

 

 

 

 

 

 

Breaker

7k~14k

18k

24k~28k

30k, 32k

36k, 38k

(A)

 

 

 

 

 

15

20

30

30

40

 

 

 

 

 

 

 

Outdoor unit

Terminal block (Pillar terminal)

Holder for power supply cord

Cover control

LS-Q096AAL

Over 5mm

Connecting cable

LS-Q096ABL

CAUTION

After the confirmation of the above conditions, prepare the wiring as follows:

1)Never fail to have an individual power circuit specifically for the air conditioner. As for the method of wiring, be guided by the circuit diagram posted on the inside of control cover.

2)The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)

3)Specification of power source.

4)Confirm that electrical capacity is sufficient.

5)See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.

6)Confirm that the cable thickness is as specified in the power source specification. (Particularly note the relation between cable length and thickness. (Refer to page 30))

7)Always install an earth leakage circuit breaker in a wet or moist area.

8)The following would be caused by voltage drop.

Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.

9)The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active(phase) conductors.

-31-

Page 31
Image 31
LG Electronics LS-Q096ADL, LS-Q096BBG, LS-Q096ACG, LS-Q076ABL, LS-Q096BEL, LS-Q076BBG Connect the cable to the outdoor unit