Installation
1. Installation of indoor, Outdoor unit
1) Selection of the best location
1.Indoor unit
•Do not have any heat or steam near the unit.
•Select a place where there are no obstacles in front of the unit.
•Make sure that condensation drainage can be conve- niently routed away.
Do not install near a doorway.
•Ensure that the space around the left and right of the unit is more than "A". The unit should be installed as high on the wall as possible, allowing a minimum of "B" from ceiling.
•Use a stud finder to locate studs to prevent unneces- sary damage to the wall.
More than "B"
More than "A"
•Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
More than 10 cm | More than 10 cm |
|
More than 70 cm |
2) Piping length and elevation
Capacity | Pipe Size | Standard | Max. | Max. | Additional | ||
|
| Length | Elevation | Length | Refrigerant | ||
(Btu/h) | GAS | LIQUID | |||||
(m) | B (m) | A (m) | (g/m) | ||||
|
|
|
|
|
|
| |
7k~14k | 3/8"(Ø9.52) | 1/4"(Ø6.35) | 4 or 7.5 | 7 | 15 | 20 | |
|
|
|
|
|
| ||
1/2"(Ø12.7) | 1/4"(Ø6.35) | 4 or 7.5 | 7 | 15 | 20 | ||
| |||||||
|
|
|
|
|
|
| |
| 1/2"(Ø12.7) | 1/4"(Ø6.35) | 4 or 7.5 | 15 | 30 | 20 | |
|
|
|
|
|
|
| |
18k~28k | 5/8"(Ø15.88) | 1/4"(Ø6.35) | 4 or 7.5 | 15 | 30 | 20 | |
|
|
|
|
|
|
| |
| 5/8"(Ø15.88) | 3/8"(Ø9.52) | 4 or 7.5 | 15 | 30 | 30 | |
|
|
|
|
|
|
| |
30k~38k | 5/8"(Ø15.88) | 3/8"(Ø9.52) | 7.5 | 15 | 30 | 30 | |
|
|
|
|
|
| ||
3/4"(Ø19.05) | 3/8"(Ø9.52) | 7.5 | 15 | 30 | 50 | ||
| |||||||
|
|
|
|
|
|
| |
| Outdoor unit |
| Indoor unit |
|
| ||
|
|
|
|
|
More than 2.3m
CAUTION
More than "B"
| A |
| A |
Indoor unit | B | B | Outdoor unit |
Install the indoor unit on the wall where the height from the floors more than 2.3 meters.
Grade |
| Clearance(cm) |
| |
| A |
| B | |
|
|
| ||
7K~28K | 10 |
| 5 | |
|
|
|
| |
30K~38K | 30 |
| 12 | |
|
|
|
|
|
2.Outdoor unit
•If an awning is built over the unit to prevent direct sun- light or rain exposure, make sure that heat radiation from the condenser is not restricted.
•Ensure that the space around the back and sides is more than 10cm. The front of the unit should have more than 70cm of space.
•Do not place animals and plants in the path of the warm air.
•Take the air conditioner weight into account and select a place where noise and vibration are minimum.
Outdoor unit | I |
|
Oil trap | A |
| |
Indoor unit |
|
B
If case more than 5m
CAUTION
•Capacity is based on standard length and maximum allowance length is on the basis of reliability.
•Oil trap should be installed every 5~7 meters.