6. When Heating does not operate
Turn ON Main Power
Operate “Heating Mode( )” by setting the desired temperature of the remote control is higher than one of the indoor temperature by 2°C at least.
In heating Mode, the indoor fan operates in case the pipe temperature is higher than 28°C.
Check the connector of intake and pipe sensor(thermistors)
•Check the related circuit of
•Check the indoor room temperature is disconnected or not (about 10KΩ /at 25°C).
•Check the indoor pipe temperature is disconnected or not (about 5KΩ /at 25°C).
Check the DC voltage on the PWB ASSEMBLY
• The details of check are as followings |
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
| |
| • Comp Relay. |
|
|
|
|
| • Outdoor fan Relay |
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check point | Comp ON |
| Comp OFF |
| Check point | Fan ON |
| Fan OFF | ||
|
|
|
|
|
|
|
|
|
|
|
|
| Between Micom | DC 5V |
| DC 0V |
| Between Micom | DC 5V |
| DC 0V | ||
| (NO.59) and GND |
|
| (NO.53) and GND |
| ||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
| Between IC01M | Below DC 1V |
| About DC |
| Between IC02M | Below DC 1V |
| About DC 12V | ||
| (NO.11) and GND |
|
| (NO.12) and GND |
| ||||||
|
|
|
|
| 12V |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • 4 way Relay |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check point | 4 way ON |
| 4 way OFF |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Between Micom | DC 5V |
| DC 0V |
|
|
|
|
|
| |
| (NO.51) and GND |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| Between IC02M | Below DC 1V |
| About DC 12V |
|
|
|
|
|
| |
| (NO.11) and GND |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|