2.2Status Display

Operation with Advanced Microprocessor Controls

2.2Status Display

The display normally shown includes the present room temperature, humidity, active status func- tions (cooling, heating, dehumidifying, humidifying), and active alarms. If no keys are pressed within 5 minutes, the system automatically returns to the Status Display. The Status Display may also be selected from the Main Menu.

2.3Main Menu <MENU/ESC>

Press the MENU/ESC key to display the Main Menu. The Menu selections include:

Status/alarm data

Setpoints/setup

Date and time

Status display

2.4Status/Alarm Data

Selecting STATUS/ALARM DATA from the Main Menu will display the following selections:

Active alarms

Operating status

Alarm history log

Run hours log

Analog sensors

2.4.1Active Alarms

This screen displays any active alarm. The alarms are numbered, #1 being the most recent. If there are no active alarms, then “NO ALARMS PRESENT” will be displayed.

2.4.2Operating Status

The Operating Status is intended to provide the user with displayed information concerning what the control is calling for the system to do.

NOTE

There may be some time lapse before a specific component matches the displayed number.

For example: The display indicates the chilled water valve is 68% open. On a new call for cooling, it takes several seconds for the valve to travel from fully closed to 68% open. So, when the display reads 68%, it may take a few seconds for the valve to actually open 68%. Also, if the display indicates a com- pressor is operating but the compressor has not yet turned on, it may be off because of the short cycle control (see 4.4.1 - Short Cycle Control).

2.4.3Alarm History Log

A history of the 10 most recent alarms is kept in nonvolatile memory complete with the date and time that the alarms occurred. The first alarm in the history is the most recent and the 10th is the oldest. If the alarm history is full (10 alarms) and a new alarm occurs, the oldest is lost and the newest is saved in alarm history location 1. The rest are moved down the list by 1. Alarm history on new units may show the results of factory testing.