Liebert 3000 6.4.1Suction Pressure, 6.4.2Discharge Pressure, 6.4.3Superheat, Suction pressures

Models: 3000

1 76
Download 76 pages 7.19 Kb
Page 54
Image 54
6.4.1Suction Pressure

Component Operation and Maintenance

6.4Refrigeration System

Each month, the components of the refrigeration system should be inspected for proper function and signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri- odic inspections can be a major factor in the prevention of most system failures.

Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors or the unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also inspect capillary and equalizer lines from the expansion valve and support as necessary.

Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture. Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The moisture indicator changes from green to yellow when moisture is present in the system.

6.4.1Suction Pressure

Suction pressure will vary with load conditions. The low pressure switch will shut the compressor down if suction pressure falls below the cut-out setting. High suction pressure reduces the ability of the refrigerant to cool compressor components and can result in compressor damage. Minimum (pres- sure switch cut-out setting) and maximum (design operating) suction pressures are in Table 18.

Table 18 Suction pressures

 

Minimum

Maximum

 

PSIG (kPa)

PSIG (kPa)

System

R–22

R–22

Air w/FSC

15 (103)

90 (620)

(Fan Speed Control)

 

 

Air w/Lee-Temp Control

20 (137)

90 (620)

(Floodback head

 

 

pressure control)

 

 

Water Cooled

20 (137)

90 (620)

 

 

 

Glycol Cooled

20 (137)

90 (620)

 

 

 

6.4.2Discharge Pressure

Discharge Pressure can be increased or decreased by load conditions or condenser efficiency. The high pressure switch will shut the compressor down at its cut-out setting. Refer to Table 19, below.

Table 19 Discharge pressures

 

 

Discharge Pressure

System Design

PSIG (kPa)

 

 

Air Cooled

260 (1795)

 

 

Water/Glycol Cooled

65-75°F (18-24°C) fluid

210 (1450)

 

 

 

 

85°F (29°C) fluid

225 (1550)

 

 

 

 

115°F (46°C) fluid

295 (2035)

 

 

 

Maximum

330 (2275)

 

 

High Pressure Cut-Out

360 (2482)

 

 

 

6.4.3Superheat

Superheat can be adjusted by the Thermostatic Expansion Value (TEV). To determine superheat:

1.Measure the temperature of the suction line at the point the TEV bulb is clamped.

2.Obtain the gauge pressure at the compressor suction valve.

3.Add the estimated pressure drop between bulb location and suction valve.

4.Convert the sum of the two pressures to the equivalent temperature.

5.Subtract this temperature from the actual suction line temperature. The difference is superheat.

46

Page 54
Image 54
Liebert 3000 manual 6.4.1Suction Pressure, 6.4.2Discharge Pressure, 6.4.3Superheat, Suction pressures, Discharge pressures