Component Operation and Maintenance
6.4Refrigeration System
Each month, the components of the refrigeration system should be inspected for proper function and signs of wear. Since, in most cases, evidence of malfunction is present prior to component failure, peri- odic inspections can be a major factor in the prevention of most system failures.
Refrigerant lines must be properly supported and not allowed to vibrate against ceilings, floors or the unit frame. Inspect all refrigerant lines every six months for signs of wear and proper support. Also inspect capillary and equalizer lines from the expansion valve and support as necessary.
Each liquid line has a sight glass that indicates liquid refrigerant flow and the presence of moisture. Bubbles in the sight glass indicate a shortage of refrigerant or a restriction in the liquid line. The moisture indicator changes from green to yellow when moisture is present in the system.
6.4.1Suction Pressure
Suction pressure will vary with load conditions. The low pressure switch will shut the compressor down if suction pressure falls below the
Table 18 Suction pressures
| Minimum | Maximum |
| PSIG (kPa) | PSIG (kPa) |
System | ||
Air w/FSC | 15 (103) | 90 (620) |
(Fan Speed Control) |
|
|
Air | 20 (137) | 90 (620) |
(Floodback head |
|
|
pressure control) |
|
|
Water Cooled | 20 (137) | 90 (620) |
|
|
|
Glycol Cooled | 20 (137) | 90 (620) |
|
|
|
6.4.2Discharge Pressure
Discharge Pressure can be increased or decreased by load conditions or condenser efficiency. The high pressure switch will shut the compressor down at its
Table 19 Discharge pressures
|
| Discharge Pressure |
System Design | PSIG (kPa) | |
|
| |
Air Cooled | 260 (1795) | |
|
| |
Water/Glycol Cooled | 210 (1450) | |
|
|
|
| 85°F (29°C) fluid | 225 (1550) |
|
|
|
| 115°F (46°C) fluid | 295 (2035) |
|
|
|
Maximum | 330 (2275) | |
|
| |
High Pressure | 360 (2482) | |
|
|
|
6.4.3Superheat
Superheat can be adjusted by the Thermostatic Expansion Value (TEV). To determine superheat:
1.Measure the temperature of the suction line at the point the TEV bulb is clamped.
2.Obtain the gauge pressure at the compressor suction valve.
3.Add the estimated pressure drop between bulb location and suction valve.
4.Convert the sum of the two pressures to the equivalent temperature.
5.Subtract this temperature from the actual suction line temperature. The difference is superheat.
46