Operation with Advanced Microprocessor with Graphics Control
Auto Restart Delay
This feature allows for the unit to restart automatically after a loss of power. The programmed value is .1 minute (6 seconds) intervals. A programmed value of zero (0) would require the user to manually press the ON/OFF switch to start the unit, i.e. no auto restart. The purpose of this feature is to pre- vent several units from starting at the same time after a loss of power. The message “Restart Delay
IR Flush Overfill (infrared humidifiers only)
An autoflush system automatically controls a water makeup valve to maintain proper level in the infrared humidifier water pan during humidifier operation. If humidification is needed and 30 hours have elapsed since the last time the humidifier was on, then the humidifier is held off until the valve completes an initial fill of the humidifier pan. This
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri- odically to add water to the pan (about 40 seconds for every
Chilled Water/Hot Water/Econ-O-Coil Flush
This feature will flush the respective coil for 3 minutes after the programmed number of hours of
Display in Degrees
The control can be set to display readings and setpoints in either degrees Fahrenheit (F) or Celsius (C).
Default Settings and Ranges
The following table lists the setup functions, their factory default values, and the allowable ranges for which they can be programmed.
Table 9 | Setup functions, default values and ranges | ||
|
|
|
|
| Function | Default | Range |
|
|
| |
Cold Start Time Delay* | 3 | 0 to 3 min (0 = no delay) | |
|
|
| |
Restart Time Delay | 0.1 | 0 to 9.9 min (0 = manual restart) | |
|
|
| |
Infrared Fill Rate | 150 | 110 to 500% | |
|
|
| |
Chilled/Hot Water Coil Flush | 24 | 0 to 99 hrs (also | |
|
|
| |
C/F Degrees | F | C or F | |
|
|
|
|
*Factory set to 0 for water cooled, glycol, and GLYCOOL units.
21