3.13.2Nonvolatile Memory

Operation with Advanced Microprocessor with Graphics Control

3.13.2Nonvolatile Memory

All critical information is stored in nonvolatile memory. Setpoints, setup parameters, and component run hours are kept inside the microcontroller in EEPROM. Information retained for data logging,

24 hour component run hour graphs, alarm history, and the water detection floor plan is kept in non- volatile RAM.

3.13.3DIP Switches

Equipment options are selected and enabled using DIP switches 1 to 7. These are located at the upper left of the control board and are labeled SW1. Switch 1 is at the top. These switches are factory set and should not require any user changes. The setting and function of the switches can be read from the LCD (see 3.8.4 - DIP Switches).

3.13.4Control Outputs

Active control outputs are indicated with LEDs on the lower section of the control board. Each LED is lit if the control output is active (on). Use these LEDs to assist in troubleshooting the system.

Table 12 Control output LEDs

LED

Control Output

 

 

R5

Heat Rejection

 

 

LLSV

Liquid Line Solenoid Valve

 

 

HGBP

Hot Gas By-Pass

 

 

C1

Compressor

 

 

RH1

Reheat Stage 1 or Hot Gas, Hot Water Reheat Solenoid

 

or SCR Reheats

RH2

Reheat Stage 2

 

 

HUM

Humidifier

 

 

FAN

Main Fan

 

 

HMV

Humidifier Make-Up Valve

 

 

LLSV2

Part Coil Solenoid Valve

 

 

28

Page 36
Image 36
Liebert 3000 manual 3.13.2Nonvolatile Memory, 3.13.3DIP Switches, 3.13.4Control Outputs, Control output LEDs