Troubleshooting

Table 23 Compressor and refrigeration system troubleshooting (continued)

 

 

 

Symptom

Possible Cause

Check or Remedy

 

 

 

 

Defective or improperly set expansion

Increase superheat or replace valve

Flooding

valve

 

 

Evaporator fan motor or belt

Correct problem or replace fan motor and/

 

 

or belts.

 

Low condensing pressure

Check head pressure control device

 

 

 

 

Slipping belts

Inspect and adjust

 

 

 

 

Compressor rotation in reverse

Check for proper power phase wiring to

Low compressor capacity or

direction.

unit and to compressor motor.

inability to pull down system

 

 

Leaking liquid line solenoid valve or dirt

Replace valve if clean; clean out valve if

 

 

in valve

dirty.

 

 

 

Compressor noisy

Loose compressor or piping support

Tighten clamps.

 

 

 

Pipe rattle

Loose pipe connections

Check pipe connections

 

 

 

 

Compression ratio too high

Check setting of high and low pressure

Compressor running hot

 

switches. Check condenser -- is it

 

 

plugged? Check that all evaporator and

 

 

condenser fans are operating properly.

 

Low-pressure switch erratic in operation

Check tubing to switch to see if clogged or

Compressor cycles intermittently

 

crimped. Check for proper switch

 

 

operation.

 

Insufficient refrigerant in system

Check for leaks, fix, and add refrigerant on

 

 

air cooled unit. Evacuate and recharge

 

 

water/glycol unit.

 

Suction service valve closed

Open valve.

 

 

 

 

Insufficient fluid flowing through

Adjust fluid regulating valve to condenser.

 

condenser or clogged condenser, or

Flush the condenser.

 

dirty air cooled condenser coils

 

 

Discharge service valve not fully open

Open valve

 

 

 

Compressor cycles continually

Faulty low pressure switch

Repair or replace.

 

 

Dirt or restriction in tubing to pressure

Check and clean tubing.

 

 

stat

 

 

 

 

 

Defective liquid line solenoid valve

Check valve and solenoid operator;

 

 

replace if necessary.

 

Plugged filter-drier

Replace filter.

 

 

 

 

High discharge pressure

Check for loss of condenser water or

Compressor motor protectors

 

blocked condenser fan or coil.

tripping or cycling

 

 

Defective overload relay

Replace.

 

 

 

 

 

High suction temperature

Reduce suction temperature by expansion

 

 

valve adjustment or provide

 

 

desuperheating.

 

Loose power or control circuit wiring

Check all power and control circuit

 

connection

connections.

 

Defective motor

Check for motor ground or short. Replace

 

 

compressor, if either condition is found.

 

Low line voltage

Check line voltage and determine location

Compressor cycles on locked rotor

 

of voltage drop.

 

Compressor motor defective

Check for motor winding short or ground.

 

 

 

 

Single phasing

Check voltage across all 3 legs at

 

 

contactor. Correct source problem.

 

Check control panel for welded

Replace defective components

Motor burnout

contactor contacts or welded overload

 

 

contacts

 

60

Page 68
Image 68
Liebert 3000 manual Compressor and refrigeration system troubleshooting

3000 specifications

The Liebert 3000 is a cutting-edge power protection solution designed to provide reliable and efficient backup power for critical applications. This uninterruptible power supply (UPS) system is engineered to safeguard sensitive electronic equipment from power disturbances, ensuring uninterrupted operations in data centers, telecommunications, and industrial environments.

One of the standout features of the Liebert 3000 is its high-efficiency design. With an efficiency rating of up to 94%, the system minimizes energy loss, resulting in lower operational costs and a reduced carbon footprint. This is particularly important in today's environmentally conscious climate, as organizations strive to meet sustainability goals while maintaining top-tier performance.

The Liebert 3000 employs advanced technologies to enhance its functionality. It incorporates online double-conversion technology, which provides a continuous supply of clean and regulated power. This technology ensures that connected loads receive stable voltage and frequency, shielding them from voltage spikes, sags, and outages. Additionally, the UPS offers features such as automatic battery testing, which helps ensure peak battery performance and reliability.

Another key characteristic of the Liebert 3000 is its modular design, allowing for flexible scalability. This means that organizations can easily expand the capacity of their UPS system as their power needs grow, without the need for extensive system overhauls. The modular architecture also facilitates simplified maintenance and reduces downtime, as individual modules can be serviced without interrupting power to the critical load.

The system is equipped with comprehensive monitoring and management capabilities. The Liebert 3000 provides real-time data on power usage, battery status, and system performance, enabling facility managers to make informed decisions and proactively address potential issues. The integration of remote management tools allows for seamless monitoring from anywhere, providing peace of mind for operators.

Overall, the Liebert 3000 combines high efficiency, advanced technology, and flexible design to deliver a robust power protection solution. Its reliability and performance make it a preferred choice for organizations seeking to protect their critical infrastructure while enhancing operational efficiency and sustainability. As businesses continue to rely on technology for their everyday operations, the Liebert 3000 stands out as a dependable safeguard against the uncertainties of power quality.