| Troubleshooting | |
Table 23 Compressor and refrigeration system troubleshooting (continued) | |||
|
|
| |
Symptom | Possible Cause | Check or Remedy | |
|
|
| |
| Defective or improperly set expansion | Increase superheat or replace valve | |
Flooding | valve |
| |
| Evaporator fan motor or belt | Correct problem or replace fan motor and/ | |
|
| or belts. | |
| Low condensing pressure | Check head pressure control device | |
|
|
| |
| Slipping belts | Inspect and adjust | |
|
|
| |
| Compressor rotation in reverse | Check for proper power phase wiring to | |
Low compressor capacity or | direction. | unit and to compressor motor. | |
inability to pull down system |
|
| |
Leaking liquid line solenoid valve or dirt | Replace valve if clean; clean out valve if | ||
| |||
| in valve | dirty. | |
|
|
| |
Compressor noisy | Loose compressor or piping support | Tighten clamps. | |
|
|
| |
Pipe rattle | Loose pipe connections | Check pipe connections | |
|
|
| |
| Compression ratio too high | Check setting of high and low pressure | |
Compressor running hot |
| switches. Check condenser | |
|
| plugged? Check that all evaporator and | |
|
| condenser fans are operating properly. | |
| Check tubing to switch to see if clogged or | ||
Compressor cycles intermittently |
| crimped. Check for proper switch | |
|
| operation. | |
| Insufficient refrigerant in system | Check for leaks, fix, and add refrigerant on | |
|
| air cooled unit. Evacuate and recharge | |
|
| water/glycol unit. | |
| Suction service valve closed | Open valve. | |
|
|
| |
| Insufficient fluid flowing through | Adjust fluid regulating valve to condenser. | |
| condenser or clogged condenser, or | Flush the condenser. | |
| dirty air cooled condenser coils |
| |
| Discharge service valve not fully open | Open valve | |
|
|
| |
Compressor cycles continually | Faulty low pressure switch | Repair or replace. | |
|
| ||
Dirt or restriction in tubing to pressure | Check and clean tubing. | ||
| |||
| stat |
| |
|
|
| |
| Defective liquid line solenoid valve | Check valve and solenoid operator; | |
|
| replace if necessary. | |
| Plugged | Replace filter. | |
|
|
| |
| High discharge pressure | Check for loss of condenser water or | |
Compressor motor protectors |
| blocked condenser fan or coil. | |
tripping or cycling |
|
| |
Defective overload relay | Replace. | ||
| |||
|
|
| |
| High suction temperature | Reduce suction temperature by expansion | |
|
| valve adjustment or provide | |
|
| desuperheating. | |
| Loose power or control circuit wiring | Check all power and control circuit | |
| connection | connections. | |
| Defective motor | Check for motor ground or short. Replace | |
|
| compressor, if either condition is found. | |
| Low line voltage | Check line voltage and determine location | |
Compressor cycles on locked rotor |
| of voltage drop. | |
| Compressor motor defective | Check for motor winding short or ground. | |
|
|
| |
| Single phasing | Check voltage across all 3 legs at | |
|
| contactor. Correct source problem. | |
| Check control panel for welded | Replace defective components | |
Motor burnout | contactor contacts or welded overload |
| |
| contacts |
|