Component Operation and Maintenance
6.4.7Water/Glycol Cooled Condensers Coaxial Condenser
Each water or glycol cooled module has a coaxial condenser which consists of a steel outside tube and a copper inside tube.
Coaxial condensers do not normally require maintenance or replacement if the water supply is clean. If your system operates at high head pressure with reduced capacity, and all other causes have been eliminated, the coaxial condenser may be obstructed and needs to be replaced.
Regulating Valve
The water regulating valve automatically regulates the amount of fluid necessary to remove the heat from the refrigeration system, permitting more fluid to flow when load conditions are high and less fluid to flow when load conditions are low. The valve consists of a brass body, balance spring, valve seat, valve disc holders, capillary tube to discharge pressure, and adjusting screw.
Standard Valve - 150 psig (1034 kPa) system for 3 & 5 ton units (Johnson Controls Valve) High Pressure Valve - 350 psig (2413 kPa) system for 5 ton units (Johnson Controls Valve)
To lower the head pressure setting, turn the square adjusting screw clockwise until the high pressure gauge indicates the desired setting.
To raise the head pressure setting, turn the adjusting screw counterclockwise until the desired set- ting is obtained.
Figure 10 Johnson Controls valve adjustment
Range
Spring
Valve |
|
Spring |
|
Guide | Range Adjustment Screw |
| |
| Top |
| Retainer |
| Insert screwdrivers under |
| the valve spring guide. |
Manual