| Troubleshooting | |
Table 24 Dehumidification troubleshooting |
|
| |
|
|
|
|
Symptom | Possible Cause | Check or Remedy |
|
|
|
|
|
| Control not calling for | Check monitor status. |
|
No dehumidification | dehumidification |
|
|
| Compressor contactor not pulling in | See 6.4.8 - Compressor Functional |
|
|
| Check and Table 23. |
|
| Compressor won't run; fuse blown or | See 6.4.8 - Compressor Functional |
|
| CB tripped | Check and Table 23. Check fuses or |
|
|
| CBs and contacts. Check line voltage |
|
Table 25 Glycol pump troubleshooting |
|
| |
|
|
| |
Symptom | Possible Cause | Check or Remedy |
|
|
|
|
|
Suddenly stops pumping | Clogged strainer or impeller | Clean out debris. |
|
|
|
|
|
Suddenly slow pumping | Clogged impeller, diffuser, or line | Clean out debris and use strainer. |
|
|
|
|
|
Excessive leakage around the pump | Worn seal or packing | Replace seal or packing. |
|
shaft while operating |
|
|
|
Performance poor | Worn impeller or seal | Replace with new impeller or seal. |
|
|
|
| |
Suction lift too high | Relocate pump closer to supply. |
| |
|
| ||
|
|
|
|
| Motor not up to speed; low voltage | Larger lead wires may be required. |
|
|
| Check for proper line voltage (±10%). |
|
| Worn bearings | Replace pump |
|
|
|
|
|
Noisy operation | Worn motor bearings | Replace pump |
|
|
|
| |
Low discharge head | Throttle |
| |
|
| ||
|
| conditions. |
|
|
|
|
|
| Debris lodged in impeller | Remove cover and clean out. |
|
|
|
|
|
| Cavitating pumps | Adjust system pressures. |
|
|
|
|
|
Table 26 Infrared humidifier troubleshooting |
|
| |
|
|
| |
Symptom | Possible Cause | Check or Remedy |
|
|
|
|
|
No humidification | Humidifier pan not filling | Check water supply. |
|
|
|
| |
| Check fill valve operation |
| |
|
|
| |
|
|
|
|
|
| Check drain stand pipe adjustment |
|
|
|
|
|
|
| Check for clogged waterline |
|
|
|
|
|
| Control not calling for humidity | Check monitor status |
|
|
|
|
|
| Humidity contact not pulling in | Check visually. If contact is made, |
|
|
| check line voltage after contactor and |
|
|
| fuses or CBs. |
|
|
| Check for open humidifier safety stat. |
|
|
| Jumper between terminals |
|
|
|
| |
|
| safety. Remove jumper. |
|
| Humidifier bulb burned out | Replace bulb. Loosen lead on old |
|
|
| bulb. Trim excess lead length on new |
|
|
| bulb to avoid shorts. |
|
61