Figure 5 Analog input jumpers

System Performance with Advanced Microprocessor Controls

Figure 5 Analog input jumpers

ENLARGED AREA

Analog input jumper location

 

 

 

 

4.5.2Water Detection Display

The water detection display is designed to graphically display the location of water under a raised floor when connected to an LT750 water detection system. The graphical floor plan screen shows a 30 x 16 grid. Each square represents one standard floor tile (approximately 2 ft. x 2 ft.).

Installation—LT750 DIP Switch Settings

Install the LT750 following the instructions in the LT750 user manual. The following additional switch selections should be made when connecting to an Advanced Microprocessor control:

DIP SW3-4—Off-(water alarm relay energizes for alarm)

DIP SW3-5—Off-(cable fault relay energizes for alarm)

Switch 1—Off-(LT750 sources power for 4-20 mA loop)

Figure 6 Connecting the LT750

TB6

2

-

+

1

TB5

3

NO

2

NC

fault

1

C

 

3

NO

TB4

NC

2

water

1

C

LT750

 

 

4 1

4.5.2Water Detection Display 4 2

4 3

4 4

4 5

4 6

4 7 4 8

Installation—LT750 DIP Switch Settings 2 4

5 0

5 1

5 5 5 6

Environmental Unit