Control Panel Description

3.0CONTROL PANEL DESCRIPTION

Refer to Figure 5.

3.1Mimic Panel

The Mimic panel consists of the following:

UPS SYSTEM 1 - PRIMARY BYPASS

UPS SYSTEM 2 - PRlMARY BYPASS

UPS SYSTEM 1 - ON BYPASS

UPS SYSTEM 2 - ON BYPASS

LOAD 1 CIRCUIT BREAKER

LOAD 2 CIRCUIT BREAKER

TIE CIRCUIT BREAKER

LOAD 1 - NORMAL

LOAD 1 - ON SYSTEM 2

LOAD 1 - SYSTEMS TIED

LOAD 1 - OFF

LOAD 2 - NORMAL

LOAD 2 - ON SYSTEM 1

LOAD 2 - SYSTEMS TIED

LOAD 2 - OFF

CONTROL STATUS - SYNCHRONIZING

CONTROL STATUS - TRANSFERRING

UPS System 1 - Primary Bypass

This light turns on when UPS System 1 is the selected Primary Bypass. When lit, the light indicates the UPS Modules of both UPS systems are synchronizing to the bypass of UPS System 1, when sys- tems are tied or in the process of transferring load.

UPS System 2 - Primary Bypass

This light turns on when UPS System 2 is the selected Primary Bypass. When lit, the light indicates that the UPS Modules of both UPS systems are synchronizing to the bypass of UPS System 2, when systems are tied or in the process of transferring load.

UPS System 1 - On Bypass

This light turns on when UPS System 1 is on Bypass.

UPS System 2 - On Bypass

This light turns on when UPS System 2 is on bypass.

Load 1 Circuit Breaker

These two lights indicate the OPEN (Red light) or CLOSED (Green light) state of the Load 1 circuit breaker.

Load 2 Circuit Breaker

These two lights indicate the OPEN (Red light) or CLOSED (Green light) state of the Load 2 circuit breaker.