Operating Instructions

Figure 12 Transfer both load feeders to one UPS

 

 

 

FROM:

 

TO:

Normal Operation

Combined Loads Operation

System 1

System 2

System 1

System 2

M1

M1

SS1

SS2

M2

M2

M1

M1

SS1

SS2

M2

M2

Tie Open

 

Momentary Tie

 

Tie Closed

 

for transfer of

 

Tie

Load 2 to

Tie

Load 1

Load 2

System 1

Load 1

Load 2

See 4.2.4 - Isolating a UPS System for Maintenance -

LEGEND: Mx =

Module

Combined Loads Operation.

SSx =

Static Bypass Switch

 

 

 

Figure 13 Both feeders on one system to normal operation

 

 

M1

FROM:

Combined Loads Operation

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

M1

TO:

Normal Operation

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

 

Tie Closed

Tie Open

 

Tie

Tie

Load 1

Load 2

Load 1

Load 2

See 4.2.6 - Returning an Isolated System to Normal

LEGEND: Mx =

Module

Operation - End Combined Loads Operation.

SSx =

Static Bypass Switch

Figure 14 Transfer 100% load on one system to 100% load on a second system (a two-step operation)

FROM:

Combined Loads Operation on System 1

 

 

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

M1

 

SS1

 

SS2

 

M2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TO:

Combined Loads Operation on System 2

 

 

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

M1

 

SS1

 

SS2

 

M2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tie Closed

Tie

Load 1 Load 2

Momentary Tie for transfer of Load 2 to System 2, then Momentary Tie for transfer of Load 1 to System 2

Tie Closed

Tie

Load 1 Load 2

See 4.2.5 - Transfer of Load Between Two Systems.

LEGEND: Mx =

Module

 

SSx =

Static Bypass Switch

34

Page 38
Image 38
Liebert Series 610 user manual See 4.2.4 Isolating a UPS System for Maintenance, Combined Loads Operation