Operating Instructions
4.0OPERATING INSTRUCTIONS
Refer to Figure 5.
4.1Initial System Start-Up
All load circuit breakers and tie circuit breakers are initially open.
1.Press the CLOSE LOAD 1 button located on the panel behind the Control door. The Load 1 breaker should close when the button is pressed.
2.Press the CLOSE LOAD 2 button located behind the Control door. The Load 2 breaker should close when the button is pushed.
NOTE
The operation can be performed with the UPS on bypass or inverter output. The
3.Once one or both UPS systems are
4.2Basic Operation
4.2.1Momentary Tie - Load Transfers
A momentary tie operation is used to transfer a critical load from a UPS system, which requires isola- tion for maintenance, to another UPS system without placing the critical load on utility bypass.
The isolated UPS system can be serviced while the critical load remains protected by a fully func- tional UPS system. Once service is complete, perform another Momentary tie operation to return the critical load to its normal UPS system. This can be done without placing the critical load on utility bypass.
4.2.2Normal Transfer Operation Configurations
Transfers of a critical load between systems can be performed from several initial system configura- tions. The guiding criteria for permitting transfers is that the critical load must remain on UPS inverter output.
Transfers to a UPS system operating on its bypass source cannot be initiated due to logic lockouts. However, a critical load initially on a UPS system’s bypass source can be transferred to the other UPS system operating on inverter output.
In addition to checking system configurations, the
The logic intelligently determines which system to synchronize with, which UPS system capacity to check, and which load(s) to check, based on which system the operator selects to transfer load. The
The
4.2.3Maintenance Procedures - Isolating Each UPS System
25