Operating Instructions

Figure 15 Normal split load operations to Continuous Tie

M1

FROM:

Normal Operation

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

M1

TO:

Continuous Tied Systems

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

Tie Open

Continuous Tie

operation for

Tie

module out of

Load 1 Load 2

service

Tie Closed

Tie

Load 1 Load 2

See 4.2.11 - Tying the UPS Systems - Continuous

LEGEND: Mx =

Module

Parallel Operations.

SSx =

Static Bypass Switch

 

 

 

Figure 16 Continuous Tie to normal split load operation

 

 

M1

FROM:

Continuous Tied Systems

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

M1

TO:

Normal Operation

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

Module returned to service

Tie

Tie Closed

Tie Open

 

Tie

Load 1 Load 2Load 1 Load 2

See 4.2.11 - Returning Parallel Systems to Normal

LEGEND: Mx =

Module

Operation - End Continuous Tie.

SSx =

Static Bypass Switch

 

 

 

Figure 17 Continuous Tie to load on one system

 

 

M1

FROM:

Continuous Tied Systems

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

M1

TO:

Combined Loads Operation

System 1

 

 

 

 

 

System 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1

 

SS1

 

SS2

 

M2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M2

Module

 

Tie Closed

returned

 

to service

Tie

Load 1

Load 2

 

Tie Closed

Tie

Load 1 Load 2

See 4.2.4 - Isolating a UPS System for Maintenance -

LEGEND: Mx =

Module

Combined Loads Operation.

SSx =

Static Bypass Switch

35

Page 39
Image 39
Liebert Series 610 user manual See 4.2.11 Tying the UPS Systems Continuous, Parallel Operations