OPERATION

B-10

 

 

 

COMPONENT STATUS LIGHTS

Each network component has a single status light. The light is a bicolor, Green/Red, LED. The purpose of the status light is to allow the operator to quickly identify that the system is working properly or, if not,

which component is causing the problem. By using the status lights the operator can quickly pinpoint the system problem to a particular component. See the following table for a complete listing and description of all status light conditions.

NOTE: The green light ON and steady indicates a normal functioning system.

STATUS LIGHT STATES

LED State

Power Source LED

LED on any other nodes (components);

 

 

Wire Feeder, Control Box Etc.

 

 

 

Off

Power Source is not turned ON or is not func-

The system component is not receiving input

 

tioning correctly.

power or is faulty.

Green LED blink-

It should only blink for a few seconds while

It should only blink for a few seconds until

ing at a normal

the system is mapping (identifying compo-

the system component (node) has been rec-

rate

nents). If blinking continues every group may

ognized. If the blinking continues at least

 

have a mapping error. (DIP switches may be

one node in the group has a mapping error

 

set incorrectly).

(DIP switches may be set incorrectly). The

 

 

node or nodes with mapping errors will be

 

 

blinking red.

 

 

There may be too many components in the

 

 

group. All components in the group will be

 

 

blinking green.

 

 

The power source bus may not be avail-

 

 

able. The bus may be being used to program

 

 

another component.

 

 

The LEDs of the power source and the

 

 

component being programmed will be solid

 

 

green.

Red LED blinking

Indicates a recoverable communication fault.

Indicates a recoverable communication fault

at a normalrate

The power source should automatically

most likely caused by one of the following.

 

recover: If it cannot recover the LED will be

More than one control box (UI) in the

 

solid red.

group. All control boxes in the group will be

 

 

blinking red.

 

 

No control box (UI) in the group. All nodes

 

 

in the group will be blinking red.

 

 

More than one node, of the same equip-

 

 

ment type, has the same group and feed

 

 

head (FH) numbers. All these nodes will be

 

 

blinking red.

 

 

The feed head DIP switches may be set to

 

 

zero. The nodes with DIP switches set to

 

 

zero will be blinking red.

 

 

The node bus may be off.

Red/Green LED

Indicates a recoverable hardware fault such

Indicates a recoverable hardware fault such

blinking at a nor-

as over temperature, overload shutdown etc.

as over temperature, overload shutdown etc.

malrate

 

Could also be an open shutdown circuit at

 

 

the feed head (leads 570, 572 with tab termi-

 

 

nals) typically used for water flow shutdown

 

 

switches.

 

 

 

POWER FEED 11