Pumps Parameters Screen:
The Pumps Screen allows access to four (4) parameters. Those parameters are as follows:
•Boiler Pump Delay - Sets the length of time the boiler pumps will run after a system heat call has been satisfied. This parameter can only be changed by the installer. The time range for this parameter is 0 minutes to 40 minutes. The default time is 30 seconds.
•HW Pump Delay - Sets the length of time the Hot Water Generation pumps (if connected) will run after a Hot Water Generation call has been satisfied. This parameter can only be changed by the installer. The time range for this parameter is 0 minutes to 40 minutes. The default time is 30 seconds.
•System Pump Delay - Sets the length of time the system pump (if connected) will run after a system heat call has been satisfied. This parameter can only be changed by the installer. The time range for this parameter is 0 minutes to 40 minutes. the default time is 30 seconds.
•System Pump Mode - Sets the configuration of the system pump. The configuration selections are:
0.The system pump will be on continuously except during outdoor shutdown.
1.The system pump will be off.
2.The system pump will be on only during a system heat call.
This parameter can only be changed by the installer. The default configuration is 2: On only during a system heat call.
Reference page 18 for information regarding changing parameters.