Lochinvar 1 Maintenance Maintenance and annual startup, Service technician, Owner maintenance

Models: 1.3 1

1 56
Download 56 pages 40.75 Kb
Page 36
Image 36
2 Maintenance

Service Manual

2 Maintenance

Maintenance and annual startup

Table 2A Service and Maintenance Schedules

Service technician

(see the following pages for instructions)

 

General:

 

 

 

• Address reported problems

 

• Inspect interior; clean and vacuum if

 

necessary;

 

 

 

• Clean condensate trap and fill with fresh

 

water

 

 

 

• Check for leaks (water, gas, flue,

 

condensate)

 

 

 

• Verify flue and air lines in good condition

 

and sealed tight

 

 

 

• Check system

water

pressure/system

UP-

piping/expansion tank

 

• Check control settings

 

 

 

START

• Check ignition and flame sense

electrodes (sand off any deposits; clean

 

ANNUAL

and reposition)

 

 

• Check wiring and connections

 

 

• Perform start-up checkout and

 

performance verification per Section 9

 

in the SYNC Installation and

 

Operation Manual.

 

 

• Flame inspection (stable, uniform)

 

• Flame signal (at least 10 microamps at

 

high fire)

 

 

 

•Clean the heat exchanger if flue

 

temperature is more than 54°F (30°C)

 

above return water temperature.

 

• Test low water flow conditions.

 

If combustion

or

performance

 

indicate need:

 

 

Clean heat exchanger

Remove and clean burner using compressed air only

Clean the blower wheel

Owner maintenance

(see the SYNC User’s Information Manual for

instructions)

 

• Check boiler area

Daily

•Check pressure/temperature

 

gauge

 

• Check vent piping

 

 

• Check air piping

 

Monthly

• Check air and vent termination

screens

 

 

 

• Check relief valve

 

 

• Check condensate drain system

 

Check

automatic

air

 

vents

 

 

 

 

• Test low water cutoff

 

Every

• Reset button (low water cutoff)

6 months

• Check

boiler

piping (gas

and

 

water) for leaks

 

 

 

• Operate relief valve

 

End

• Shut boiler down (unless boiler

of season

used for hot water generation)

months

 

Table 2A Service and Maintenance Schedules 36 Service technician

Page 36
Image 36
Lochinvar 1.3 Maintenance Maintenance and annual startup, Service technician, Owner maintenance, General, If combustion