3 Troubleshooting (continued)

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

Internal Fault

The main control board has detected an

• Replace the main control board.

 

internal fault.

 

 

 

 

 

Writing to

The main control board has detected an

• Replace the main control board.

 

Memos

internal fault.

 

 

 

 

 

CRC Parameters

The main control board has detected an

• Replace the main control board.

 

 

internal fault.

 

 

 

 

 

No Error Stored

The main control board has detected an

• Press

the RESET button on the

SMART

 

internal fault.

TOUCH display panel.

 

 

 

 

 

• Inspect the heat exchanger. Reference page 40 of

 

 

this manual for the procedure on how to clean the

 

 

flue side of the heat exchanger.

 

Flue Temp

 

• Inspect the flue sensor and associated wiring.

The stack temperature has exceeded the

Measure the resistance of

the flue sensor and

Shutdown

compare to Table 3C on page 45 of this manual.

set parameters for the boiler.

 

Replace the sensor if necessary.

 

 

 

 

 

 

• Verify that the vent/air intake pipes are properly

 

 

installed and that there are no obstructions.

 

 

 

• Replace the main control board.

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

SYNC

Installation

and

Operation

Manual

 

 

for the proper piping methods for the SYNC boiler.

 

 

• Check for voltage to the boiler pump motor on a call

Delta T

The temperature rise across the heat

for heat. If voltage is not present, check the wiring

back to the pump relay. Replace the pump relay if

Shutdown

exchanger has exceeded the set parameters

necessary.

 

 

 

 

for the boiler.

 

 

 

 

• If 120 VAC is present on a call for heat and the boiler

 

 

 

 

pump is not operating, replace the pump.

 

 

 

• Verify that the boiler pump is set to the proper speed

 

 

or that the pump is the proper size. Reference

 

 

Section

6 - Hydronic Piping of the

SYNC

 

 

Boiler Installation and Operation Manual for boiler

 

 

pump specifications.

 

 

 

 

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

system. Refer to Section 6 - Hydronic Piping of the

Outlet Temp

 

SYNC

Installation

and

Operation

Manual

Outlet water temperature has exceeded the

for the proper piping methods for the SYNC boiler.

Shutdown

• Check for voltage to the boiler pump motor on a call

 

maximum outlet water temperature.

for heat. If voltage is not present, check wiring back

 

 

 

 

to the pump relay. Replace the pump relay if

 

 

necessary.

 

 

 

 

 

• If 120 VAC is present on a call for heat and the boiler

 

 

pump is not operating, replace the pump.

 

 

 

 

 

 

 

 