Lochinvar 1 Troubleshooting, Fault, Description, Corrective Action, Automatic Reset High Limit

Models: 1.3 1

1 56
Download 56 pages 40.75 Kb
Page 50
Image 50
Automatic Reset High Limit:

Service Manual

3 Troubleshooting

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

 

 

Automatic Reset High Limit:

 

 

 

• Verify that the system is full of water and that all air

 

 

 

has been properly purged from the system.

 

 

 

• Verify that the boiler is piped properly into the heating

 

 

 

system. Refer to Section 6 - Hydronic Piping of the

 

 

 

SYNC Installation and Operation Manual

 

 

 

for the proper piping methods for the SYNC.

 

 

 

• Check voltage to boiler pump motor on a call for

 

 

 

heat. If voltage is not present, check wiring back to

 

 

 

the pump relay.

 

 

 

• Replace the pump relay if necessary.

 

 

 

• If 120 VAC is present on a call for heat and the boiler

 

 

 

pump is not operating, replace the pump.

Automatic Reset

 

 

• If the system pump is a variable speed pump, ensure

High Limit / HEX-

 

 

that the system flow is not less than the boiler flow.

Temp SW

Either the auto-reset high limit (optional),

• If operating on either an inlet or system supply

(will require a manual

reset once the condition

or the O-temp heat exchanger switch as

sensor, check temperature setting of the main control

board.

has been corrected. Press

opened.

 

 

• If the high limit has tripped, check setting of the

the RESET button on the

 

 

display to reset.)

 

 

device.

 

 

 

 

 

 

• Check resistance of water sensors and compare to

 

 

 

Table 3B on page 45 of this manual. Replace sensor

 

 

 

if necessary.

 

 

 

• Replace high limit.

 

 

 

 

 

 

 

HEX Temp SW:

 

 

 

• Check continuity across two contacts. Wires should

 

 

 

be connected at both poles of normally closed switch.

 

 

 

• Inspect the rear of the inner combustion chamber

 

 

 

at the burner level, for refractory breakdown/missing.

 

 

 

Replace the refractory if no damage to the heat

 

 

 

exchanger as a result of the burner, otherwise,

 

 

 

replace the heat exchanger.

 

 

 

• Faulty O-temp heat exchanger switch. Replace

 

 

 

switch.

 

 

 

 

 

 

 

• Vent/air intake lengths exceed the maximum allowed

 

 

 

lengths. Refer to Section 2 - General Venting of the

 

 

 

SYNC Installation and Operation Manual for

Blower RPM’s

The actual fan rpm is 30% lower than what

proper lengths.

• Check for obstruction or blockage in the vent/air

Too Low

is being called for.

Reference the Burners

Screen information

on page 32 of this

intake pipes or at terminations.

(will require a manual

• Check the wiring connections at the fan and at the

manual.

 

reset once the condition

 

has been corrected. Press

 

 

main control board.

 

 

• Replace the fan.

the RESET button on the

 

 

display to reset.)

 

 

• Replace the main control board.

 

 

 

 

 

 

 

 

Blown fuse.

 

• Replace fuse F4 on the control board, see page 43 of

 

 

this manual.

 

 

 

 

 

 

 

HEX Temp SW: 50 Manual background

Page 50
Image 50
Lochinvar 1.3 Troubleshooting, Fault, Description, Corrective Action, Automatic Reset High Limit, HEX Temp SW