2 Maintenance

Test low water flow conditions

NOTICE

This test is to be carried out once the

SYNC boiler is completely piped in

 

 

with adequate gas and water flow.

 

Once the test is completed, ensure

 

that the isolation valve is opened up to

 

allow full water flow.

Test procedure

1.Set the SYNC to operate with the demand configuration parameter set to 1 (Cascade Set Point Thermostat- Based).

NOTE: This can be accomplished by selecting the demand configuration parameter in the Service/Setup Menu. See Section 1 of this manual for complete details of the SmartTouch controls.

2.Set the system setpoint to the max user setpoint. Max user setpoint will allow the boiler to operate without reaching this setpoint. The boiler will require a load large enough to dissipate a large portion of the heat it is generating.

3.Simulate a call for heat by placing a jumper wire across the enable contacts on the low voltage terminal strip located at the rear of the unit (FIG. 2-3).

4.Allow the unit to progress through its normal diagnostics and pre-purge programming.

5.Allow the unit to fire and operate until the temperatures stabilize. This occurs when the inlet and outlet

temperatures are rising together and the Delta T ( T) is maintained.

6.When the unit stabilizes, begin to slowly shut off the isolation valve on the outlet piping of the boiler (see FIG. 2-4). This will begin to restrict the flow and simulate a low flow condition.

7.While slowly shutting off the isolation valve, refer to the Burner Screen to watch the behavior of the boiler. On this screen, you will witness each individual control module modulating its’ respective burner’s firing rate

 

while reacting to the rising

T.

8.

When the

T reaches

50˚F for an individual heat

 

exchanger, the control for the heat exchanger will

 

attempt to modulate the firing rate down to protect it

 

from low flow conditions.

 

9.

When the

T reaches

60˚F for an individual heat

exchanger, the control module for the heat exchanger will turn off the respective burner.

NOTE: The Temperature Menu will show the inlet and outlet temperatures for each individual heat exchanger.

Service Manual

10.Restrict the isolation valve until both control modules have shut down. If both control modules have been shut down, the test was successful.

11.Disconnect the jumper wire from the low voltage terminal strip connected in step 3.

12.If necessary, reset the demand configuration in the Service/ Setup Menu to the required operational mode.

NOTE: See Section 1 of this manual for complete details of the SmartTouch controls.

13.Completely open the isolation valve on the outlet piping of the boiler.

14.Resume operation.

NOTE: This lockout is a soft lockout. Once the T has decreased to an acceptable level and there is a call for heat, the unit will fire again to meet the demand.

Figure 2-3Low voltage terminal strip & enable contacts

LOW VOLTAGE CONNECTION BOARD

 

1

ALARM

 

 

2

CONTACTS

 

 

3

RUN TIME

 

 

4

CONTACTS

 

 

5

LOUVER

 

 

6

PROVING

 

 

7 MODULE 2

 

 

8

FLOW SWITCH

 

9 MODULE 1

 

 

10 FLOW SWITCH

 

11 TANK

 

ENABLE

12 THERMOSTAT

 

13 R ENABLE

 

CONTACTS

14 W

 

 

 

 

LBL20052 REV B

 

15 SHIELD GND

MOD

 

16 A

 

 

17 B

 

BUS

 

18 SHIELD GND

 

 

 

19

(+)

0 - 10V INPUT

 

20

(-)

 

21 SYSTEM

 

 

22 SENSOR

 

 

23 OUT DOOR

 

 

24 SENSOR

 

 

25 TANK

 

 

 

26 SENSOR

 

 

27 SHIELD GND

CASCADE

 

28 B

 

 

29 A

 

 

 

30 SHIELD GND

 

Figure 2-4Adjust outlet isolation valve

ADJUST OUTLET

ISOLATION VALVE

ONLY

41

Page 41
Image 41
Lochinvar 1.3 service manual Test low water flow conditions, Test procedure

1.3, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.