Lochinvar 1.3 Test low water flow conditions, Maintenance, Test procedure, Service Manual

Models: 1.3 1

1 56
Download 56 pages 40.75 Kb
Page 41
Image 41
Test low water flow conditions

2 Maintenance

Test low water flow conditions

NOTICE

This test is to be carried out once the

SYNC boiler is completely piped in

 

 

with adequate gas and water flow.

 

Once the test is completed, ensure

 

that the isolation valve is opened up to

 

allow full water flow.

Test procedure

1.Set the SYNC to operate with the demand configuration parameter set to 1 (Cascade Set Point Thermostat- Based).

NOTE: This can be accomplished by selecting the demand configuration parameter in the Service/Setup Menu. See Section 1 of this manual for complete details of the SmartTouch controls.

2.Set the system setpoint to the max user setpoint. Max user setpoint will allow the boiler to operate without reaching this setpoint. The boiler will require a load large enough to dissipate a large portion of the heat it is generating.

3.Simulate a call for heat by placing a jumper wire across the enable contacts on the low voltage terminal strip located at the rear of the unit (FIG. 2-3).

4.Allow the unit to progress through its normal diagnostics and pre-purge programming.

5.Allow the unit to fire and operate until the temperatures stabilize. This occurs when the inlet and outlet

temperatures are rising together and the Delta T ( T) is maintained.

6.When the unit stabilizes, begin to slowly shut off the isolation valve on the outlet piping of the boiler (see FIG. 2-4). This will begin to restrict the flow and simulate a low flow condition.

7.While slowly shutting off the isolation valve, refer to the Burner Screen to watch the behavior of the boiler. On this screen, you will witness each individual control module modulating its’ respective burner’s firing rate

 

while reacting to the rising

T.

8.

When the

T reaches

50˚F for an individual heat

 

exchanger, the control for the heat exchanger will

 

attempt to modulate the firing rate down to protect it

 

from low flow conditions.

 

9.

When the

T reaches

60˚F for an individual heat

exchanger, the control module for the heat exchanger will turn off the respective burner.

NOTE: The Temperature Menu will show the inlet and outlet temperatures for each individual heat exchanger.

Service Manual

10.Restrict the isolation valve until both control modules have shut down. If both control modules have been shut down, the test was successful.

11.Disconnect the jumper wire from the low voltage terminal strip connected in step 3.

12.If necessary, reset the demand configuration in the Service/ Setup Menu to the required operational mode.

NOTE: See Section 1 of this manual for complete details of the SmartTouch controls.

13.Completely open the isolation valve on the outlet piping of the boiler.

14.Resume operation.

NOTE: This lockout is a soft lockout. Once the T has decreased to an acceptable level and there is a call for heat, the unit will fire again to meet the demand.

Figure 2-3Low voltage terminal strip & enable contacts

LOW VOLTAGE CONNECTION BOARD

 

1

ALARM

 

 

2

CONTACTS

 

 

3

RUN TIME

 

 

4

CONTACTS

 

 

5

LOUVER

 

 

6

PROVING

 

 

7 MODULE 2

 

 

8

FLOW SWITCH

 

9 MODULE 1

 

 

10 FLOW SWITCH

 

11 TANK

 

ENABLE

12 THERMOSTAT

 

13 R ENABLE

 

CONTACTS

14 W

 

 

 

 

LBL20052 REV B

 

15 SHIELD GND

MOD

 

16 A

 

 

17 B

 

BUS

 

18 SHIELD GND

 

 

 

19

(+)

0 - 10V INPUT

 

20

(-)

 

21 SYSTEM

 

 

22 SENSOR

 

 

23 OUT DOOR

 

 

24 SENSOR

 

 

25 TANK

 

 

 

26 SENSOR

 

 

27 SHIELD GND

CASCADE

 

28 B

 

 

29 A

 

 

 

30 SHIELD GND

 

Figure 2-4Adjust outlet isolation valve

ADJUST OUTLET

ISOLATION VALVE Test procedureFigure 2-4Adjust outlet isolation valve

ONLY

Manual background 41 Manual background

Page 41
Image 41
Lochinvar 1.3 Test low water flow conditions, Maintenance, Test procedure, Service Manual, 4 Adjust outlet isolation valve