Service Manual
3 Troubleshooting (continued)
Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION |
| |
|
| • Vent/air intake lengths exceed the maximum allowed | ||
|
| lengths. Refer to Section 2 - General Venting of the | ||
Blower RPM’s |
| SYNC Installation and Operation Manual for | ||
| proper lengths. |
| ||
Too High |
| • Check for obstruction or blockage in the vent/air | ||
(will require a manual | The actual fan rpm is 30% higher than what | |||
reset once the condition | is being called for. | intake pipes or at terminations. |
| |
has been corrected. Press |
| • Check the wiring connections at the fan and at the | ||
the RESET button on the |
| |||
display to reset.) |
| main control board. |
| |
|
| • Replace the fan. |
| |
|
| • Replace the main control board. |
| |
|
|
| ||
Sensor Open |
| • Check the sensors and their associated wiring. | ||
(will require a manual |
| Repair or replace the sensor or wiring if damaged. | ||
reset once the condition | Either the inlet water or outlet water | • Measure the resistance of the sensors and compare | ||
has been corrected. Press | temperature sensor has been disconnected. | the resistance to the tables on page 45 | of this | |
the RESET button on the |
| manual. |
| |
display to reset.) |
|
| ||
| • Replace the sensor if necessary. |
| ||
|
|
| ||
|
|
|
| |
Sensor Shorted |
| • Check the sensors and their associated | wiring. | |
| Repair or replace the sensor or wiring if damaged. | |||
(will require a manual |
| |||
Either the inlet water or outlet water | • Measure the resistance of the sensors and compare | |||
reset once the condition | ||||
has been corrected. Press | temperature sensor has been shorted. | the resistance to the tables on page 45 of this | ||
the RESET button on the |
| manual. |
| |
display to reset.) |
| • Replace the sensor if necessary. |
| |
|
|
| ||
|
|
| ||
Flue Sensor |
| • Check the sensor and its associated wiring. Repair | ||
| or replace the sensor or wiring if damaged. |
| ||
Open / Removed |
| • Measure the resistance of the sensors and compare | ||
(will require a manual |
| |||
The flue sensor has been disconnected or | the resistance to the tables on page 45 of this | |||
reset once the condition | ||||
has been corrected. Press | removed from the flue. | manual. |
| |
the RESET button on the |
| • Replace the sensor in flue. |
| |
display to reset.) |
|
| ||
| • Replace the sensor if necessary. |
| ||
|
|
| ||
|
|
|
| |
Flue Sensor |
| • Check the sensor and its associated wiring. | Repair | |
Shorted |
| or replace the sensor or wiring if damaged. |
| |
(will require a manual |
| • Measure the resistance of the sensors and compare | ||
reset once the condition | The flue sensor has been shorted. | the resistance to the tables on page 45 of this | ||
has been corrected. Press | ||||
the RESET button on the |
| manual. |
| |
display to reset.) |
| • Replace the sensor if necessary. |
| |
|
|
|
| |
Louver Proving |
|
|
| |
Switch |
| • Check function of remote devices. |
| |
(will require a manual |
|
| ||
An optional remote proving switch is not | • Check for loose or misplaced jumper if proving switch | |||
reset once the condition | ||||
has been corrected. Press | making. | is not installed. |
| |
the RESET button on the |
|
|
| |
display to reset.) |
|
|
| |
|
|
|
| |
| Sensors equipped with an internal limit (such | • Check the tank temperature. |
| |
Tank Open | as the Lochinvar Squire® Indirect Tank), the | • Repair or replace the sensor wiring if damaged. | ||
| limit has opened due to temperature (195°F) | • Replace the sensor if necessary. |
| |
| or the sensor has become disconnected. |
| ||
|
|
|
|
51