2 Maintenance (continued)

Check flame signal

1.At high fire the flame signal shown on the display should be at least 10 microamps.

2.A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode.

3.See Section 3 - Troubleshooting in this manual for other procedures to deal with low flame signal.

Review with owner

1.Review the SYNC User’s Information Manual with the owner.

2.Emphasize the need to perform the maintenance schedule specified in the SYNC User’s Information Manual (and in this manual as well).

3.Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior.

4.Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.

Cleaning boiler heat exchanger

For recommended materials; including brush, appropriate extension(s), refractory cover, and detailed instructions see Table 2B - Heat Exchanger Cleaning Kits.

1.Shut down boiler:

Follow the “To Turn Off Gas to Appliance” instructions for the boiler in the SYNC Installation and Operation Manual.

Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain.

2.Allow time for the boiler to cool to room temperature if it has been firing.

3.Remove the nuts securing the heat exchanger access cover to the heat exchanger and set aside.

4.Remove the heat exchanger access cover, burner, and gas/air arm assembly.

 

WARNING

The boiler contains ceramic fiber

 

 

 

 

materials. Use care when handling these

 

 

 

 

 

 

 

 

materials per instructions on page 3 of

 

 

 

 

this manual. Failure to comply could

 

40

 

 

result in severe personal injury.

 

 

 

 

 

 

Service Manual

5.Remove the condensate hose from the heat exchanger end. Connect a field supplied 3/4” diameter hose to a drain pan. Using field supplied means, cover the refractory in the back of the combustion chamber of the heat exchanger.

6.Use a vacuum cleaner to remove any accumulation on the boiler heating surfaces. Do not use any solvent.

7.Brush the heat exchanger while dry using a nylon bristle brush. Caution: DO NOT use a metal brush. Re-vacuum the heat exchanger.

8.Finish cleaning using a clean cloth dampened with warm water. Rinse out debris with a low pressure water supply.

9.Allow the heat exchanger to thoroughly dry.

10.Remove the field supplied rear refractory cover from the back of the combustion chamber of the heat exchanger and reassemble.

11.Close isolation valves on piping to isolate boiler from system. Attach a hose to the boiler drain and flush boiler thoroughly with clean water by using purging valves to allow water to flow through the water make-up line to the boiler.

12.Perform start-up and check-out procedures in the Check Flame and Combustion Section of the SYNC Installation and Operation Manual.

13.Replace the access cover and restore boiler to operation.

Table 2B Heat Exchanger Cleaning Kits

Model

 

Kit

Part

Component

Number

Number

Number

Description

 

 

 

 

 

 

 

 

MSC20083*

Nylon 4” Wheel Brush*

 

 

 

 

 

SB 1.0 - 1.5

KIT30064

MSC20085

1/4” x 12” Drill Extension

 

 

 

 

 

 

 

 

MSC20086

1/4” x 24” Drill Extension

 

 

 

 

 

 

 

* Do NOT use a metal brush. Only use

CAUTION

the kit provided brush or an equivalent

 

 

 

 

replacement nylon brush.