2 General venting (continued)
Stainless steel vent
This product has been approved for use with stainless steel using only FasNSeal vent systems.
WARNING Use only the materials, vent systems, and terminations listed in Table 2F. DO NOT
mix vent systems of different types or manufacturers. Failure to comply could result in severe personal injury, death, or substantial property damage.
Installation & Operation Manual
| NOTICE | Installation of a stainless steel vent system |
| should adhere to the stainless steel vent | |
|
| manufacturer’s installation instructions |
|
| supplied with the vent system. |
|
|
|
Figure |
NOTICE PVC/CPVC or ABS is acceptable air inlet pipe material.
REMOVE PVC/CPVC VENT
CONNECTOR WHEN
INSTALLING STAINLESS STEEL
NOTICE
NOTICE
The installer must use a specific vent starter adapter at the flue collar connection, supplied by the vent manufacturer to adapt to its vent system. See Table 2F for approved vent adapters. Discard CPVC starter piece.
Installations must comply with applicable national, state, and local codes. Stainless steel vent systems must be listed as a
The SYNC uses model specific combustion air intake and vent piping sizes as detailed in Tables 2A and 2B.
NOTICE
Increasing or decreasing combustion air or vent piping to sizes not specified in this manual is not authorized.
Table 2F Approved Stainless Steel Terminations and Adapters
STAINLESS STEEL VENT TERMINATION KITS
Kit Part Number | Model | Component Description | |
|
|
| |
|
| 6" PVC x 6" Stainless Steel Adapter | |
KIT30028 | SB 1000 - 1500 |
| |
6" Stainless Steel Vent Termination | |||
|
|
| |
|
| 6" Stainless Steel Air Inlet | |
|
|
| |
|
| 6" PVC x 6" Stainless Steel Adapter | |
|
|
| |
KIT30029 | SB 1300 - 1500 | 6" Stainless Steel x 7" Stainless Steel Adapters (2) | |
| |||
7" Stainless Steel Vent Termination | |||
|
| ||
|
|
| |
|
| 7" Stainless Steel Air Inlet | |
|
|
|
21