Lochinvar 5 operation manual Determine boiler location continued, Installation & Operation Manual

Models: 5

1 68
Download 68 pages 3.38 Kb
Page 13
Image 13
TABLE - 1B

Installation & Operation Manual

1 Determine boiler location (continued)

Figure 1-7_Combustion Air from Outside - Single Opening

4.If a single combustion air opening is provided to bring combustion air in directly from the outdoors, the opening must be sized based on a minimum free area of one square inch per 3000 Btu/hr (7 cm2 per kW). This opening must be located within 12" (30 cm) of the top of the enclosure (see FIG. 1-7).

Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN B149.1. Check all local code requirements for combustion air.

All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers.

Where two openings are provided, one must be within 12" (30cm) of the ceiling and one must be within 12" (30cm) of the floor of the equipment room. Each opening must have net free area as specified in the chart below (Table 1B). Single openings shall commence within 12" (30cm) of the ceiling.

￿CAUTION Under no circumstances should the equipment room ever be under negative

pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.

The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system.

The result is improper combustion and a non-warrantable, premature appliance failure.

EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be corrected immediately.

TABLE - 1B

MINIMUM RECOMMENDED COMBUSTION

AIR SUPPLY TO EQUIPMENT ROOM

 

FIG. 1-4

FIG. 1-5

FIG. 1-6

FIG. 1-7

 

*Outside Air from

*Outside Air from

**Inside Air from

 

Model

2 Openings Directly from

2 Ducts Delivered from

2 Ducts Delivered from

*Outside Air from

Number

Outdoors

Outdoors

Interior Space

1 Opening Directly

 

Top

Bottom

Top

Bottom

Top

Bottom

from Outdoors, in2

 

Opening, in2

Opening, in2

Opening, in2

Opening, in2

Opening, in2

Opening, in2

 

1.0

250

250

500

500

1000

1000

333

(1613 cm2)

(1613 cm2)

(3226 cm2)

(3226 cm2)

(6452 cm2)

(6452 cm2)

(2149 cm2)

 

1.3

325

325

650

650

1300

1300

433

(2097 cm2)

(2097 cm2)

(4194 cm2)

(4194 cm2)

(8388 cm2)

(8388 cm2)

(2794 cm2)

 

1.5

375

375

750

750

1500

1500

500

(2420 cm2)

(2420 cm2)

(4839 cm2)

(4839 cm2)

(9678 cm2)

(9678 cm2)

(3226 cm2)

 

*Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. The above requirements are for the appliance only; additional gas fired appliances in the equipment room will require an increase in the net free area to supply adequate combustion air for all appliances.

**Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *“Tight Construction”. For buildings of *“Tight Construction”, provide air openings into the building from outside.

*No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *“Tight Construction”.

*”Tight Construction” is defined as a building with less than 0.40 ACH (air changes per hour).

13

 

Page 13
Image 13
Lochinvar 5 Determine boiler location continued, Installation & Operation Manual, B Minimum Recommended Combustion