Installation & Operation Manual
3 Sidewall direct venting
Figure
8. PVC/CPVC terminations are designed to accommodate any |
wall thickness of standard constructions per the directions |
found in this manual. |
7’ (2.1 M) MIN ABOVE ANY
PUBLIC WALKWAY
IF LESS
THAN 10’ (3 M)
36” (914 MM)
MIN
FORCED AIR
INLET
BIRD
SCREEN
(TYPICAL)
9. Stainless steel terminations are designed to penetrate walls |
with a thickness up to 9.25 inches of standard construction. |
Figure
| VENT AIR |
AIR PIPING | CENTERLINE WIDTH |
VENT PIPING |
|
| VENT PLATE |
WALL PLATE | VENT CAP |
|
Prepare wall penetrations
1.Use the factory supplied wall plate as a template to locate the vent and air intake holes and mounting holes.
Air pipe penetration:
a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.
Vent pipe penetration:
a. Cut a hole for the vent pipe. For either combustible |
or noncombustible construction, size the vent pipe |
hole with at least a 1/2 inch clearance around the |
vent pipe outer diameter: |
• 7½ inch hole for 6 inch vent pipe |
• 8½ inch hole for 7 inch vent pipe |
GALVANIZED |
THIMBLE |
Table 3C Sidewall Vent Centerline Dimensions
Model | Air | Vent | Centerline Width |
|
|
|
|
All | 6" | 6" | 7 3/4" |
Figure
Drill 3/16" diameter holes for inserting the plastic anchors into the wall.
2. | For Polypropylene Only: Install the vent and air intake |
| sidewall adapters from Table 2E on page 20 into the vent |
| plate. Slide the sidewall retaining bracket down the |
| sidewall adapters flush to the vent plate (FIG. |
3. | For PVC/CPVC Only: Install the vent and air intake |
| piping through the wall into the vent plate openings. |
| Use RTV silicone sealant to seal the air pipe. Use the |
| cement/primer listed in Table 2C on page 19 to seal the |
| vent pipe. |
4. | Mount and secure the vent plate to the wall, using stainless |
| steel screws. |
5. | Seal all gaps between the pipes and wall. Seal around the |
SIDEWALL ADAPTER (AIR)
SIDEWALL ADAPTER (VENT)
WALL
PLATE
SIDEWALL
RETAINING
PLATE
VENT
PLATE
VENT
CAP
| plate to the wall assuring no air gaps. |
6. | Assemble the vent cap to the vent plate (see FIG.’s |
| and |
| cap screw hole openings and securely attach the vent cap |
| to the vent plate. |
7. | Seal all wall cavities. |
GALVANIZED | IMG00085 |
THIMBLE |
|
24