Installation & Operation Manual

6 Gas connections

Table 6A Natural Gas Pipe Size Chart

 

 

 

 

 

 

 

TABLE - 6A

 

 

 

 

 

 

 

 

 

 

 

 

GAS PIPING SIZE CHART

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nominal

 

 

 

 

Length of Pipe in Straight Feet

 

 

 

 

 

Maximum

Iron Pipe

 

 

 

 

 

 

 

 

 

Capacity of Pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in Thousands

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of Btu/hr for

Inches

10

20

30

40

50

60

70

80

90

 

100

125

150

175

200

 

gas pressures of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14 Inches Water

2,150

1,500

1,210

1,020

923

830

769

707

666

 

636

564

513

472

441

 

Column (0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PSIG) or less and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

4,100

2,820

2,260

1,950

1,720

1,560

1,440

1,330

1,250

 

1,180

1,100

974

871

820

a pressure drop

 

of 0.5 Inch Water

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

 

1,900

1,700

1,540

1,400

1,300

Column (Based

 

on NAT GAS,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1025 Btu/hr per

3

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

 

3,300

3,000

2,720

2,500

2,340

 

Cubic Foot of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas and 0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

23,500

16,100

13,100

11,100

10,000

9,000

8,300

7,690

7,380

 

6,870

6,150

5,640

5,130

4,720

Specific Gravity)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check inlet gas supply

NOTICE

CSA or UL listed flexible gas connections are

acceptable, but you must exercise caution to

 

ensure that the line has adequate capacity to

 

allow your boiler to fire at full rate. Consult

 

with local codes for proper installation or

 

service procedures.

￿WARNING DO NOT adjust or attempt to measure gas valve outlet pressure. Attempting to alter

or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage.

The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load.

If you experience a pressure drop greater than 1 inch w.c. (249 Pa), the meter, regulator, or gas line is undersized or in need of service. Perform the steps below when checking inlet gas supply:

1.Turn the main power switch to the “OFF” position.

2.Shut off gas supply at the manual gas valve in the gas piping to the appliance.

3.Remove the 1/8" pipe plug on the flange to the field supplied gas shutoff valve and install a suitable 1/8" fitting (field supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the 1/8" fitting is installed as shown in FIG. 6-3.

4.Slowly turn on the gas supply at the field installed manual gas valve.

5.Turn the power switch to the “ON” position.

6.Adjust the temperature set point on the control panel of the SMART TOUCH control module to call for heat.

7.Observe the gas supply pressure as the burner fires at 100% of rated input. Percent of burner input will be displayed on the Burner Screen.

8.Ensure inlet pressure is within specified range. Minimum and maximum gas supply pressures are specified in this section of the manual.

9.If gas supply pressure is within normal range and no adjustments are needed, proceed on to Step 11.

10.If the gas pressure is out of range, contact the gas utility, gas supplier, qualified installer or service agency to determine the necessary steps to provide proper gas pressure to the control.

11.Turn the power switch to the “OFF” position.

12.Shut off the gas supply at the manual gas valve in the gas piping to the appliance.

13.Remove the manometer from the pressure tap on top of the gas valve. Remove the 1/8" (3 mm) field supplied fitting and reinstall the pipe plug removed in Step 3.

36

Page 36
Image 36
Lochinvar 5 operation manual Check inlet gas supply, GAS Piping Size Chart

5 specifications

Lochinvar 5 is a cutting-edge residential boiler designed to meet the heating needs of modern homes while ensuring high efficiency and user convenience. As one of the latest offerings from Lochinvar, a trusted name in the heating industry, the Lochinvar 5 combines advanced technology with robust features that make it a top choice for homeowners and contractors alike.

One of the standout characteristics of the Lochinvar 5 is its impressive energy efficiency. It boasts an AFUE (Annual Fuel Utilization Efficiency) rating of up to 95%, which significantly reduces fuel consumption compared to traditional heating systems. This not only translates to lower energy bills for homeowners but also minimizes the environmental impact, aligning with the growing demand for sustainable energy solutions.

The Lochinvar 5 employs a highly efficient modulating burner technology that optimizes fuel usage based on real-time heating demand. This ensures that the boiler operates at peak efficiency, providing consistent warmth without unnecessary energy waste. The inclusion of advanced controls further enhances its performance, allowing users to adjust settings easily and monitor usage through a user-friendly digital display.

Durability and reliability are also paramount in the design of the Lochinvar 5. Constructed with high-quality materials, this boiler is built to withstand the rigors of daily use and provide long-lasting performance. Its compact design allows for flexible installation options, making it suitable for various residential settings, even where space is limited.

In addition to its impressive performance metrics, Lochinvar 5 is equipped with smart technology features that cater to the needs of modern consumers. Wi-Fi connectivity enables remote monitoring and control via a mobile app, giving homeowners the ability to adjust settings on the go. This feature not only enhances user convenience but also allows for proactive maintenance and alerts, helping to prevent potential issues before they arise.

Safety is a key consideration in the design of Lochinvar 5. It includes multiple safety features, such as a sealed combustion system that minimizes the risk of carbon monoxide leaks and an advanced monitoring system that ensures optimal operating conditions at all times.

In conclusion, the Lochinvar 5 stands out as an exceptional choice for those seeking a reliable, efficient, and smart residential heating solution. Its combination of advanced technologies, user-friendly features, and robust construction make it a leading option in the boiler market, ready to meet the demands of today’s homeowners. With an eye on energy efficiency and ease of use, Lochinvar 5 is well-equipped to provide comfortable, cost-effective heating for years to come.