Installation & Operation Manual
4 Sidewall direct venting
Sidewall termination – optional concentric vent: Models 400 - 601 Only
Figure 4-9 Concentric Vent Dimensional Drawing - Models 400 - 601
"A" |
"B" DIA. |
"C" DIA. |
3" |
(76 MM) |
"G" |
"B" DIA. PVC VENT / EXHAUST
"D" |
"E" |
"H" DIA.
"F"
A | B | C | D | E | F | G | H |
60" | 4" | 6" | 21 1/8" | 10" | 7 5/8" | 3" | 6 5/8" |
(1524 MM) | (102 MM) | (152 MM) | (537 MM) | (254 MM) | (194 MM) | (76 MM) | (168 MM) |
|
|
|
|
|
|
|
|
NOTICE | Instead of cementing the smaller pipe to |
the rain cap, a | |
| screw may be used to secure the two (2) |
| components together when field disassembly |
| is desired for cleaning (see FIG. |
6.Install the Y concentric fitting and pipe assembly through the structure’s hole from an inside wall.
NOTICE | Do not allow insulation or other materials | |
to accumulate inside the pipe assembly | ||
| ||
| when installing through the hole. |
WARNING
WARNING
When using the alternate screw assembly method, drill a clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used. Failure to drill adequate holes may cause cracking of PVC components, allowing combustion products to be recirculated. Failure to follow this warning could result in personal injury or death.
Do not operate the appliance with the rain cap removed or recirculation of combustion products may occur. Water may also collect inside the larger combustion air pipe and flow to the burner enclosure. Failure to follow this warning could result in product damage or improper operation, personal injury, or death.
7.Install the rain cap and small diameter pipe assembly into the Y concentric fitting and large pipe assembly from an outside wall. Ensure small diameter pipe is fastened tightly into the rubber adapter for #CVK3007 installations.
8.Secure the assembly to the structure as shown in FIG.
NOTICE | Ensure termination location clearance | |
dimensions are as shown in FIG. | ||
| If assembly needs to be extended to allow | |
NOTICE | ||
sidewall thickness requirement, the two | ||
| ||
| (2) pipes supplied in the kit may be | |
| replaced by using the same diameter, | |
| ||
| for CVK3007. Do not extend dimension |
Figure 4-10 Rain Cap to Vent Pipe Alternate Assembly
STAINLESS STEEL SCREW
(FIELD SUPPLIED)
DRILL CLEARANCE HOLE IN
RAIN CAP & PILOT HOLE
IN VENT PIPE
| D* more than 60 inches (1524 mm) (see | |
| FIG. | |
| If assembly depth needs to be reduced, | |
NOTICE | ||
dimension D can be as short as possible. | ||
|
28