3 General venting (continued)

Air inlet pipe materials:

The air inlet pipe(s) must be sealed. Choose acceptable combustion air inlet pipe materials from the following list:

PVC, CPVC or ABS

Dryer Vent or Sealed Flexible Duct (not recommended for rooftop air inlet)

Galvanized steel vent pipe with joints and seams sealed as specified in this section.

Type “B” double-wall vent with joints and seams sealed as specified in this section.

AL29-4C, stainless steel material to be sealed to specification of its manufacturer.

*Plastic pipe may require an adapter (not provided) to transition between the air inlet connection on the appliance

Installation & Operation Manual

When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume.

￿ DANGER

Failure to properly seal all joints and seams

as required in the air inlet piping may

 

 

result in flue gas recirculation, spillage

 

of flue products and carbon monoxide

 

emissions causing severe personal injury

 

or death.

Stainless steel vent

This product has been approved for use with stainless steel using the manufacturers listed in Table 3A.

and the plastic air inlet pipe.

￿WARNING

Use only the materials, vent systems, and terminations listed in Table 3B.

￿WARNING

Using vent or air intake materials other than those specified, failure to properly seal all seams and joints or failure to follow vent pipe manufacturer’s instructions can result in personal injury, death or property damage. Mixing of venting materials will void the warranty and certification of the appliance.

DO NOT mix vent systems of different types or manufacturers, unless listed in this manual. Failure to comply could result in severe personal injury, death, or substantial property damage.

NOTICE

Installations must comply with applicable

national, state, and local codes. Stainless

 

steel vent systems must be listed as a

NOTICE

The use of double-wall vent or insulated

material for the combustion air inlet pipe is

 

recommended in cold climates to prevent

 

the condensation of airborne moisture in

 

the incoming combustion air.

Sealing of Type “B” double-wall vent material or galvanized vent pipe material used for air inlet piping on a sidewall or vertical rooftop Combustion Air Supply System:

a.Seal all joints and seams of the air inlet pipe using either Aluminum Foil Duct Tape meeting UL Standard 723 or 181A-P or a high quality UL Listed silicone sealant such as those manufactured by Dow Corning or General Electric.

b.Do not install seams of vent pipe on the bottom of horizontal runs.

c.Secure all joints with a minimum of three sheet metal screws or pop rivets. Apply Aluminum Foil Duct Tape or silicone sealant to all screws or rivets installed in the vent pipe.

d.Ensure that the air inlet pipes are properly supported.

The PVC, CPVC, or ABS air inlet pipe should be cleaned and sealed with the pipe manufacturer’s recommended solvents and standard commercial pipe cement for the material used. The PVC, CPVC, ABS, Dryer Vent or Flex Duct air inlet pipe should use a silicone sealant to ensure a proper seal at the appliance connection and the air inlet cap connection. Dryer vent or flex duct should use a screw type clamp to seal the vent to the appliance air inlet and the air inlet cap. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.

 

UL-1738 approved system for the United

 

States and a ULC-S636 approved system

 

for Canada.

 

Installation of a stainless steel vent system

NOTICE

should adhere to the stainless steel vent

 

manufacturer’s installation instructions

 

supplied with the vent system.

 

The installer must use a specific vent starter

NOTICE

adapter at the flue collar connection,

 

supplied by the vent manufacturer to

 

adapt to its vent system. See Table 3B for

 

approved vent adapters. Discard CPVC

 

starter piece.