Installation & Operation Manual

5 Vertical direct venting (continued)

Vent/air termination – vertical

Prepare roof penetrations

Multiple vent/air terminations

 

1.Air pipe penetration:

a.Cut a hole for the air pipe. Size the air pipe hole as close as desired to the air pipe outside diameter.

2.Vent pipe penetration:

a.Cut a hole for the vent pipe. For either combustible or noncombustible construction, size the vent pipe hole with at least a 1/2 inch clearance around the vent pipe outer diameter:

5½ inch hole (140 mm) hole for 4 inch (102 mm) vent pipe

7½ inch hole (191 mm) hole for 6 inch (152 mm) vent pipe

b.Insert a galvanized metal thimble in the vent pipe hole (when required by local codes).

3.Space the air and vent holes to provide the minimum spacing shown in FIG.’s 5-1A and 5-1B, page 30.

4.Follow all local codes for isolation of vent pipe when passing through floors, ceilings, and roofs.

5.Provide flashing and sealing boots sized for the vent pipe and air pipe.

Termination and fittings

1.Prepare the vent termination coupling and the air termination elbow (FIG.’s 5-1A and 5-1B) by inserting bird screens. Bird screens should be obtained locally.

2.The air piping must terminate in a down-turned 180° return bend as shown in FIG.’s 5-1A and 5-1B. Locate the air inlet pipe no further than 2 feet (.6 m) from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream.

3.The vent piping must terminate in an up-turned coupling as shown in FIG. 5-1A. The top of the coupling must be at least 1 foot (.3 m) above the air intake. When the vent termination uses a rain cap as illustrated in FIG. 5-1B maintain at least 36" (914 mm) above the air inlet. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than

2feet (.6 m) apart and with the vent termination at least

1foot (.3 m) above the air intake.

4.Maintain the required dimensions of the finished termination piping as shown in FIG.’s 5-1A and 5-1B.

5.Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.

1.When terminating multiple Knight XL boilers, terminate each vent/air connection as described in this manual (FIG. 5-2).

￿WARNING Terminate all vent pipes at the same height and all air pipes at the same height to

avoid recirculation of flue products and the possibility of severe personal injury, death, or substantial property damage.

2.Place roof penetrations to obtain minimum clearance of 12 inches (305 mm) between edge of air intake elbow and adjacent vent pipe of another boiler for U.S. installations (see FIG. 5-2). For Canadian installations, provide clearances required by CSA B149.1 Installation Code.

3.The air inlet of a Knight XL boiler is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents.

Figure 5-2Vertical Terminations with Multiple Boilers

12" (305 MM) MINIMUM VERTICALLY FROM VENT OUTLET TO ANY AIR INLET

 

 

VENT

 

AIR

12" (305 MM) MINIMUM FROM EDGE

 

 

VENT

 

OF AIR INTAKE PIPE TO ADJACENT

AIR

 

VENT PIPE FROM ANOTHER BOILER

 

 

Figure 5-3Alternate Vertical Terminations with Multiple Boilers

VENT

VENT

12" (305 MM) MINIMUM VERTICALLY FROM VENT OUTLET TO ANY AIR INLET

AIR

AIR

31

Page 31
Image 31
Lochinvar 400, 801 operation manual Prepare roof penetrations, Multiple vent/air terminations

400, 801 specifications

The Lochinvar 801,400 is a cutting-edge solution in the realm of high-efficiency commercial water heating. This model represents a significant advancement in the design and functionality of water heaters, catering primarily to the demands of large-scale facilities like hotels, hospitals, and large industrial operations.

One of the standout features of the Lochinvar 801,400 is its impressive heating capacity, which can produce up to 801,400 BTUs, making it suitable for high-demand applications. This output is crucial for establishments that require a consistent supply of hot water, such as commercial kitchens and laundry facilities. The robust design ensures that it can handle peak demand periods without compromising performance.

Another significant aspect is the innovative use of advanced technology in its operation. The Lochinvar 801,400 integrates smart controls that enhance its efficiency and ease of operation. These controls allow for precise monitoring and adjustment of water temperatures, ensuring that the system operates within optimal parameters while maximizing energy savings. The intelligent monitoring system can provide real-time updates, making it easier for facility managers to keep track of performance and address maintenance needs proactively.

The construction of the Lochinvar 801,400 incorporates durable materials that not only enhance the longevity of the unit but also offer resistance to corrosion and wear. This durability translates into lower maintenance costs and an extended lifespan for the unit, making it a worthwhile investment for businesses.

Moreover, the Lochinvar 801,400 is designed with energy efficiency in mind. It boasts a high thermal efficiency rating, which reduces operational costs and minimizes the carbon footprint of heating operations. This efficiency is critical in today’s environmentally conscious market, where businesses are seeking to reduce their energy consumption and comply with strict regulations.

The design of the Lochinvar 801,400 also prioritizes safety, featuring innovative safety controls and fail-safes that protect both the unit and the users.

In summary, the Lochinvar 801,400 offers a combination of high capacity, advanced technology, durability, and energy efficiency, making it an excellent choice for commercial water heating solutions. As industries continue to evolve, the demand for reliable and efficient water heating solutions like the Lochinvar 801,400 will only increase.