3 General venting

6.Priming and Cementing:

a.Handle fittings and pipes carefully to prevent contamination of surfaces.

b.Apply a liberal even coat of primer to the fitting socket.

c.Apply a liberal even coat of primer to the pipe end to approximately 1/2" beyond the socket depth.

d.Apply a second primer coat to the fitting socket.

e.While primer is still wet, apply an even coat of approved cement to the pipe equal to the depth of the fitting socket.

Table 3A Vent Pipe, and Fittings

f.While primer is still wet, apply an even coat of approved cement to the fitting socket.

g.Apply a second coat of cement to the pipe.

h.While the cement is still wet, insert the pipe into the fitting, if possible twist the pipe a 1/4 turn as you insert it. NOTE: If voids are present, sufficient cement was not applied and joint could be defective.

j.Wipe excess cement from the joint removing ring or beads as it will needlessly soften the pipe.

All vent pipe materials and fittings must comply with the following:

Item

Material

Standards for installation in:

United States

Canada

 

 

 

PVC Plastic Pipe, Schedules 40, 80, & 120

ANSI/ASTM D1785

 

 

PVC Plastic Pipe Fittings, Schedule 40

ANSI/ASTM D2466

CPVC and PVC venting must be ULC-S636

 

 

 

 

PVC Plastic Pipe Fittings, Schedule 80

ANSI/ASTM D2467

Vent pipe and

Certified. IPEX is an approved manufacturer

fittings

PVC - DWV Pipe and Fittings

ANSI/ASTM D2665

in Canada supplying vent material listed to

 

 

 

ULC-S636.

 

CPVC Plastic Pipe, Schedule 40 & 80

ANSI/ASTM F441

 

 

 

CPVC Plastic Pipe Fittings, Schedule 80

ANSI/ASTM F439

 

 

 

 

 

 

AL29-4C

UL1738

ULC-S636

 

NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE

 

Approved Stainless Steel Vent Manufacturers

 

Make

 

Model

ProTech Systems (Simpson Dura-Vent Co.)

 

FasNSeal Vent / FasNSeal Flex* Vent

Z-Flex (Nova Flex Group)

 

Z-Vent

Heat Fab (Selkirk Corporation)

 

Saf-T Vent

*Use of FasNSeal Flex smooth inner wall vent is to be used in vertical or near vertical sections only, taking precaution to ensure no sagging occurs of the vent system. Connect to the FasNSeal rigid vent using specially designed adapters and sealing method, see manufacturer’s instructions.

PVC/CPVC air intake/vent connections

1.Combustion Air Intake Connector (FIG.’s 3-9 and 3-10) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.

2.Vent Connector (FIG.’s 3-9 and 3-10) - Used to provide a passageway for conveying combustion gases to the outside. Transition fittings are provided with the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.

Figure 3-9Near Boiler PVC/CPVC Venting - Models 400 - 601

AIR

VENT

*

* 4” CPVC STREET ELBOW MAY BE SUBSTITUTED

4" CPVC PIPE SUPPLIED WITH

BOILER MUST BE USED FOR VENT CONNECTION

NOTE: CPVC VENT OR STAINLESS STEEL PIPE AND

VENT FITTINGS MUST BE USED IN CLOSET AND

ALCOVE INSTALLATIONS.

18

Figure 3-10Near Boiler PVC/CPVC Venting -

Models

701 - 801

 

VENT

 

AIR

 

6” COUPLING

(FIELD SUPPLIED)

6” CPVC

STARTER

PIECE

(FACTORY SUPPLIED)

THE 6” STAINLESS STEEL ADAPTER SUPPLIED

WITH THE BOILER MUST BE USED FOR VENT

CONNECTION TO PVC/CPVC. THE 6” CPVC

STARTER PIECE MUST BE USED FOR PVC ONLY.

Page 18
Image 18
Lochinvar 801, 400 operation manual PVC/CPVC air intake/vent connections, Vent Pipe, and Fittings

400, 801 specifications

The Lochinvar 801,400 is a cutting-edge solution in the realm of high-efficiency commercial water heating. This model represents a significant advancement in the design and functionality of water heaters, catering primarily to the demands of large-scale facilities like hotels, hospitals, and large industrial operations.

One of the standout features of the Lochinvar 801,400 is its impressive heating capacity, which can produce up to 801,400 BTUs, making it suitable for high-demand applications. This output is crucial for establishments that require a consistent supply of hot water, such as commercial kitchens and laundry facilities. The robust design ensures that it can handle peak demand periods without compromising performance.

Another significant aspect is the innovative use of advanced technology in its operation. The Lochinvar 801,400 integrates smart controls that enhance its efficiency and ease of operation. These controls allow for precise monitoring and adjustment of water temperatures, ensuring that the system operates within optimal parameters while maximizing energy savings. The intelligent monitoring system can provide real-time updates, making it easier for facility managers to keep track of performance and address maintenance needs proactively.

The construction of the Lochinvar 801,400 incorporates durable materials that not only enhance the longevity of the unit but also offer resistance to corrosion and wear. This durability translates into lower maintenance costs and an extended lifespan for the unit, making it a worthwhile investment for businesses.

Moreover, the Lochinvar 801,400 is designed with energy efficiency in mind. It boasts a high thermal efficiency rating, which reduces operational costs and minimizes the carbon footprint of heating operations. This efficiency is critical in today’s environmentally conscious market, where businesses are seeking to reduce their energy consumption and comply with strict regulations.

The design of the Lochinvar 801,400 also prioritizes safety, featuring innovative safety controls and fail-safes that protect both the unit and the users.

In summary, the Lochinvar 801,400 offers a combination of high capacity, advanced technology, durability, and energy efficiency, making it an excellent choice for commercial water heating solutions. As industries continue to evolve, the demand for reliable and efficient water heating solutions like the Lochinvar 801,400 will only increase.