Lochinvar 400, 801 Near boiler piping connections, Circulator sizing, Variable speed pump option

Models: 400 801

1 80
Download 80 pages 32.08 Kb
Page 39
Image 39

Installation & Operation Manual

6 Hydronic piping (continued)

12.Boiler purge valve:

Field supplied. The boiler purge valve is used to remove entrapped air from the heat exchanger during start-up.

13.System temperature sensor:

Lochinvar supplies a system temperature sensor. The sensor is to be installed in the heating loop downstream from the boiler hot water piping and heating loop junction. The sensor should be located far enough downstream to sense system diluted water temperature.

14.Y-Strainer:

Field supplied. A Y-strainer or equivalent multipurpose strainer is recommended at the inlet of the heat exchanger to remove system particles from older hydronic systems and protect newer systems.

Circulator sizing

The Knight XL heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graphs in FIG’s 6-5 and 6-6 for pressure drop through the Knight XL heat exchanger.

Near boiler piping connections

Figure 6-4ANear Boiler Piping w/Y-Strainer

Figure 6-4BNear Boiler Piping w/Low Loss Header

SYSTEM PUMP

 

 

 

SYSTEM SENSOR

 

 

M

 

 

O E

 

 

T

T

AIR SEPARATOR

 

 

S

 

SY

DRAIN

 

 

 

(TYPICAL)

 

M

M

 

 

 

O

AIR VENT VALVE

R

E

F

S

 

 

 

T

 

 

Y

 

LOW LOSS HEADER

S

 

 

 

 

 

(TYPICAL)

 

 

 

 

EXPANSION TANK

 

FAST FILL VALVE

 

INDIRECT

 

 

 

DRAIN

 

M

DOMESTIC

 

HOT WATER

O

VALVE

F

 

 

R

 

 

 

O

TANK

 

 

 

T

 

Y-STRAINER (RECOMMENDED)

BOILER PUMP

TO FLOOR

DRAIN

Variable speed pump option

DIRT SEPARATOR

SYSTEM SENSOR

SYSTEM PUMP

O

T

M

E

T

S

Y

S

Y-STRAINER (RECOMMENDED)

BOILER PUMP

 

M

M

 

O

 

R

E

F

 

T

 

 

S

 

 

Y

 

 

S

 

 

DOMESTIC HOT

WATER PUMP INDIRECT

M

DOMESTIC

HOT WATER

O

F

R

 

O

TANK

 

T

 

Variable speed pump setup

Before operation, ensure the following:

-Pump is set for an input signal of 0 - 10VDC by the dip switches on the pump control

-Pump is set for external signal control (if applicable)

-Pump is set for linear output (if applicable)

-If pump does not come equipped with a 0 - 10 VDC input option, an optional module will be required from the vendor

TO FLOOR

DRAIN

39

Page 39
Image 39
Lochinvar 400, 801 operation manual Near boiler piping connections, Circulator sizing, Variable speed pump option