3. Operation
"Battery" tab
| Personalizable function | Default setting | Options |
|
|
|
|
|
|
| Once a week |
| "Battery test" intervals | Every day | Once a month |
|
|
| No test |
|
|
|
|
| 20% remaining battery | 40% remaining battery | |
|
| backup time | backup time |
|
|
|
|
| Charger | Standard | CLA (2, 4 or 8 hours) |
|
|
|
|
"Output" tab
Rated | 230 V | 200 |
|
|
|
Rated | 50 Hz | 60 Hz |
|
|
|
Tolerance for | ± 5% | ± 1% to ± 10% , in 1% steps |
|
|
|
Alarm threshold for overload | 100% | 0 to 100%, in 10% steps |
|
|
|
Restart inverter after short circuit | Disabled | Enabled (click to add check) |
|
|
|
"By-pass" tab
Authorized voltage range for transfer to bypass | 187 V to 265 V (for | 187 V to 265 V, |
if fault or overload | 230 V rated voltage) | in 1V steps |
|
|
|
Authorized frequency range for transfer to bypass | ± 10% | ± 1% to ± 10%, in 1% steps |
if fault or overload |
|
|
|
|
|
Transfer to bypass if overload | Enabled | Disabled (click to remove check) |
|
|
|
Transfer to bypass following a fault, whatever | Disabled | Enabled (click to add check) |
the conditions on the |
|
|
|
|
|
The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).
100%
95%
90%
66%
50%
Available power as a percentage of the rated power
84
Voltage in V
Fig. 1