3. Operation

"Battery" tab

 

Personalizable function

Default setting

Options

 

 

 

 

 

 

 

Once a week

 

"Battery test" intervals

Every day

Once a month

 

 

 

No test

 

 

 

 

 

"Low-battery shutdown warning" threshold

20% remaining battery

40% remaining battery

 

 

backup time

backup time

 

 

 

 

 

Charger

Standard

CLA (2, 4 or 8 hours)

 

 

 

 

"Output" tab

Rated AC-power source voltage (see figure 1)

230 V

200 V-208 V-220 V-240 V

 

 

 

Rated AC-power source frequency

50 Hz

60 Hz

 

 

 

Tolerance for AC-power source frequency

± 5%

± 1% to ± 10% , in 1% steps

 

 

 

Alarm threshold for overload

100%

0 to 100%, in 10% steps

 

 

 

Restart inverter after short circuit

Disabled

Enabled (click to add check)

 

 

 

"By-pass" tab

Authorized voltage range for transfer to bypass

187 V to 265 V (for

187 V to 265 V,

if fault or overload

230 V rated voltage)

in 1V steps

 

 

 

Authorized frequency range for transfer to bypass

± 10%

± 1% to ± 10%, in 1% steps

if fault or overload

 

 

 

 

 

Transfer to bypass if overload

Enabled

Disabled (click to remove check)

 

 

 

Transfer to bypass following a fault, whatever

Disabled

Enabled (click to add check)

the conditions on the AC-power source

 

 

 

 

 

The value selected for the rated UPS voltage impacts on the power available at UPS output (see the diagram below).

100%

95%

90%

66%

50%

Available power as a percentage of the rated power

84

Voltage in V

Fig. 1