MGE UPS Systems 12 kVA, 4.5 kVA, 6 kVA, 9 kVA user manual Reconnecting the connection module

Models: 4.5 kVA 9 kVA 6 kVA 12 kVA

1 32
Download 32 pages 24.9 Kb
Page 27
Image 27

Reconnecting the connection module

17

18

19

21

2

30

8

4. Maintenance

1. Secure the connection module 8 using the two screws 30 .

2.Reconnect the connection cable(s) to the battery module(s).

3.Switch the battery circuit breaker(s) 2 to the ON position and check that LED 17 is ON.

Check that UPS personalization settings still correspond to the equipment to be supplied (see section 3.5).

4.Press button 21 and wait 20 seconds.

5.Check that LED 18 is ON.

If LED 18 is not ON, do not switch the manual bypass to the intermediate position and call the after-sales support department.

6.Turn the manual bypass switch 7 from the BYPASS position to the intermediate position and check that LED 17 is OFF.

7.Turn the manual bypass switch 7 from the intermediate position to the NORMAL position. LED 17 goes OFF and LED 19 goes ON.

The connected equipment is again protected by the UPS.

51033212EN/AC - Page 27

Page 27
Image 27
MGE UPS Systems 12 kVA, 4.5 kVA Reconnecting the connection module, Connected equipment is again protected by the UPS