4. Maintenance

4.2 Replacement of the electronic module

Disconnecting the connection module

Before turning the switch,

see the manual

NORMAL

BY-PASS

1.

Turn the manual bypass switch 7 , located behind the UPS

(see section 1.2), from the NORMAL to the intermediate

position.

2.

Check that LED 18 is ON before continuing to the BYPASS

position.

bypass

7

18

If LED 18 is not ON, do not switch to the BYPASS position and call the after-sales support department.

3.Turn the manual bypass switch 7 from the intermediate position to the BYPASS position.

The connected equipment is supplied by the AC- power source, via the manual bypass.

21

Before turning the switch,

see the manual

NORMAL

BY-PASS

4.Shut down the UPS by pressing button 21 (return to the OFF position).

5.Switch the battery circuit breaker(s) 2 to the OFF position.

6.Remove the two fixing screws 30 to free the connection module 8 (see next page).

7.Remove the connection cable(s) from the battery module(s).

The UPS can be replaced. The connected equipment is supplied by the AC-power source.

Page 26 - 51033212EN/AC

Page 26
Image 26
MGE UPS Systems 9 kVA, 4.5 kVA, 6 kVA, 12 kVA Replacement of the electronic module, Disconnecting the connection module