MGE UPS Systems 6 kVA, 4.5 kVA, 9 kVA, 12 kVA user manual Options, EPO Emergency Power Off

Models: 4.5 kVA 9 kVA 6 kVA 12 kVA

1 32
Download 32 pages 24.9 Kb
Page 9
Image 9

1. Presentation

1.3 Options

EPO (Emergency Power Off)

Available for both tower and rack versions of UPSs with standard backup times and for the battery extensions, the EPO (Emergency Power Off) option lets you simultaneously switch off the UPS battery circuit breaker and the upstream circuit breaker of your installation by connecting both of them to a single emergency off button (not supplied).

For more details, visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/epo.htm

Transformer for galvanic isolation or earthing arrangement change

 

Comet EXtreme

Comet EXtreme

 

Transfo 4.5 - 6 kVA

Transfo 9 - 12 kVA

 

 

 

Nominal power

6 kVA

12 kVA

 

 

 

Nominal current

32 A

63 A

Input voltage

230V (+15%, -20%)

230V (+15%, -20%)

Voltage drop

2.2%

1.7%

Frequency

50/60 Hz (+/-10%)

50/60 Hz (+/-10%)

 

 

 

Isolation (EN 61558-1-2-4)

3.75 kV / 5 M ohms

3.75 kV / 5 M ohms

 

 

 

Operating temperature

From 0° to +40° C

From 0° to +40° C

 

 

 

Max. operating rel. humidity

95%

95%

Derating / altitude

Pn-10% > 1000 m

Pn-10% > 1000 m

Natural ventilation

IP20 ANAN

IP20 ANAN

Dimensions HxWxD (tower)

443 x 173 x 465 mm

443 x 216 x 465 mm

Dimensions HxWxD (rack 4U)

177 x 483 x 462 mm

177 x 483 x 462 mm

Weight (tower)

44 kg

62 kg

Weight (rack)

48 kg

67 kg

 

 

 

Important: to simplify installation, connect the Comet EXtreme Transformer downsteam of the UPSs.

Visit our Web site: www.mgeups.com/products/pdt230/smallups/extreme/transfo.htm

Battery extensions for UPS backup times of 80 minutes

Battery extensions for 4.5 or 6 kVA Comet EXtreme:

 

 

 

 

 

Comet

 

 

Comet

 

 

Comet

Comet

Comet

EXtreme

+

EXtreme

+

EXtreme

+

EXtreme

EXtreme

EXB

EXB

EXB

EXB

4.5 /

6 kVA

 

 

 

 

 

4.5 /

 

 

4.5 /

 

 

 

4.5 /

4.5 /

 

 

 

 

 

 

6 kVA

 

 

6 kVA

 

 

6 kVA

6 kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Comet EXtreme offers a standard backup time of 9/12 minutes.

To increase backup time, it is possible to connect Comet EXtreme EXB modules to the UPSs.

Visit our Web site: www.mgeups.com/

products/pdt230/smallups/extreme/ guide.htm.

4.5 kVA:

12 min

30 min

54 min

80 min

6 kVA:

9 min

23 min

40 min

75 min

51033212EN/AC - Page 9

Page 9
Image 9
MGE UPS Systems 6 kVA, 4.5 kVA Options, EPO Emergency Power Off, Battery extensions for UPS backup times of 80 minutes