LED | Status | Diagnosis |
|
|
|
24 | On | Input signal On from relay K4 to indicated wire stuck in weld joint |
|
|
|
| Off | Input signal Off from relay K4 to indicate wire is not stuck in weld joint |
|
|
|
25 | On | Indicates +5 volts dc is present on automation module PC9 |
|
|
|
| Off | Indicates +5 volts dc is not present on automation module PC9 |
|
|
|
26 | On | Input signal on from relay K5 for flow (shielding gas or coolant) present |
|
|
|
| Off | Input signal off from relay K5 for flow (shielding gas or coolant) not present |
|
|
|
27 | On | Indicates −15 volts dc is present on automation interface module PC9 |
|
|
|
| Off | Indicates −15 volts dc is not present on automation interface module PC9 |
|
|
|
28 | On | Indicates +15 volts dc is present on automation interface module PC9 |
|
|
|
| Off | Indicates +15 volts dc is not present on automation interface module PC9 |
|
|
|
29 | On | Input signal on from relay K6 for arc detected |
|
|
|
| Off | Input signal off from relay K6 for no arc detected |
|
|
|
30, 31 | On | See Network Status Table in Section |
|
|
|
| Off | See Network Status Table in Section |
|
|
|
32 | On | Input signal on for aux. relay energized |
|
|
|
| Off | Input signal off for aux. relay energized |
|
|
|
33 | On | Input signal on touch sensor touch detected |
|
|
|
| Off | Input signal off touch sensor touch not detected |
|
|
|