4-10. Electrical Service Guide For 230 VAC
Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.
| 60 Hz Single Phase | |
|
| |
Input Voltage | 230 | |
|
| |
Input Amperes At Rated Output | 25 | |
|
| |
Max Recommended Standard Fuse Rating In Amperes |
| |
Circuit Breaker 1, | 30 | |
Normal Operating 3 | 35 | |
Min Input Conductor Size In AWG 4 | 12 | |
Max Recommended Input Conductor Length In Feet (Meters) | 79 | |
(24) | ||
| ||
|
| |
Min Grounding Conductor Size In AWG 4 | 12 | |
Reference: 2005 National Electrical Code (NEC) (including article 630) |
|
1Choose a circuit breaker with
2
3“Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and above).
4Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table 310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.
4-11. Extension Cord Data
.When calculating max. cord length, remember to include conductor length from line disconnect device to input power receptacle.
| Input Power |
|
|
|
Input Voltage | Phase | Hertz | Conductor Size | Max. Cord Length |
|
|
|
|
|
115 V | 1 | 60 | 10 AWG | 34 ft (10 m) |
|
|
|
|
|
230 V | 1 | 60 | 12 AWG | 79 ft (24 m) |
|
|
|
|
|