Mitsubishi Electronics MXZ-32SV service manual LEV control

Models: MXZ-32SV

1 44
Download 44 pages 62.89 Kb
Page 20
Image 20
Thermostat ON in
COOL or DRY mode
Thermostat OFF in HEAT mode
Thermostat ON in HEAT mode

11-1.LEV control

Linear expansion valve (LEV) is controlled by "Thermostat ON" commands given from each unit.

Indoor unit status

LEV opening

Stop of all indoor unit

Opening before stop 500 pulse in 15 minutes

When outdoor unit is operating,

COOL : 5 pulse (full closed)

some indoor unit stops and

HEAT : 59 pulse (slightly opened)

some operates.

Thermostat OFF in

When the outdoor unit operation (When the other indoor unit operate): 5 pulse.

When outdoor unit stops. (When the other indoor unit stops or thermo off):

COOL or DRY mode

Maintain LEV opening before stop 500 pulse in 15 minutes

 

LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency:

Ex.) Opening 130 pulse in standard opening 1 Minimum 80 pulse, Maximum 205 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)

• After starting operation, adjustment in accordance with intake super heat, discharge temperature is included in standard opening. w1

Note: LEV opening in each frequency at DRY operation and COOL operation is the same. However, velocity and compressor operation frequency controls are different. See 11-2 Operational frequency range

(As far as the indoor unit velocity control goes, refer to DRY operation in MICROPROCESSOR CONTROL in the indoor unit service manual.)

• When the outdoor unit operates. (When the other indoor unit operates): 59 pulse

• When the outdoor unit stops. (When the other indoor unit stops or thermo off): Maintain LEV opening before stop 500 pulse in 15 minutes.

• LEV opening for each indoor unit is determined by adding adjustment in accordance with the number of operating unit and the capacity class to standard opening, based on the operation frequency:

Ex.) Opening 120 pulse in standard opening 1 Minimum 70 pulse, Maximum 165 pulse. (Capacity code 4 at 1 unit operation) (Capacity code 1 at 4 unit operation)

After starting operation, opening becomes the one that adjustment in accordance with discharge temperature was added to basic opening. w1

w1 LEV opening when the outdoor unit operating: Upper limit 500, Lower limit 59

Determination of LEV standard opening in each indoor unit

The standard opening is on the straight line, which connects an each standard point in the section where divided into seven according to the operation frequency of compressor as shown in the figure below.

(LEV opening is controlled in proportion to the operation frequency.)

Note: Opening is adjusted at the standard opening according to the indoor unit conditions.

However, inclination of standard opening in each point of opening does not change with the original curve.

Add opening provided in Difference in Capacity in the table below to the standard opening from 1 to 8, when capacity of the indoor unit is excluding code 1.

Add opening provided in Difference in Operation number in the table below to determined LEV opening for each indoor unit, when 2, 3 or 4 indoor units are operated at the same time.

Note: Even when the adjusted standard opening exceeds the driving range from 59 to 500 pulse, actual driving output opening is in a range from 59 to 500 pulse.

< Calculation example of LEV opening >

Cool operation: Compressor frequency 70Hz: 2 unit ON: 18class (170-150)p(80-60)o(70-60)+150+75-30=205 pulse

Standard opening

(Pulse)

1

2

3

4

5

6

7

8

200

 

 

 

 

 

 

 

 

220

 

 

 

 

 

 

 

 

210

 

 

 

 

 

 

 

opening

190

 

 

 

 

 

 

 

160

 

 

 

 

 

 

 

 

180

 

 

 

 

 

 

COOL

 

170

 

 

 

 

 

 

LEV

140

 

 

 

 

 

 

HEAT

 

150

 

 

 

 

 

 

 

 

130

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

7

20

40

60

80

100

120

140

Operation frequency of compressor (Hz) : F

20

Page 20
Image 20
Mitsubishi Electronics MXZ-32SV service manual LEV control