(3) LEV opening correction by discharge temperature

When LEV correction output is 0 pulse by the suction super heat at cool or dry operation, or dry operating, correct LEV is cor- rected according to the following table.

The target discharge temperature is determined according to frequency zone and number of operation unit of the compressor.

Correct the LEV opening according to difference between the target discharge temperature and discharge temperature.

11-2.Operational frequency range

Number of

capacity

 

COOL

 

DRY

 

HEAT

 

 

 

 

 

 

operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

cord

Min.

Max.

Rated

 

Min.

Max.

Defrost

Rated

 

 

 

 

 

 

1

 

40

24

 

 

62

62

36

 

 

 

 

 

1

2

18

52

33

25

18

70

70

49

 

 

 

 

 

3

68

46

 

 

80

80

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

85

82

 

 

86

86

80

 

 

 

 

 

 

2

 

80

70

 

 

90

95

80

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

105

80

 

 

90

100

88

 

 

 

 

 

2

5

20

40

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

110

90

 

 

110

100

100

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

3

6

30

120

93

58

30

120

100

108

Note: When the fan speed of indoor unit is total

 

7

 

 

 

 

 

 

 

 

Lo notch, restrict the maximum frequency is

 

8

 

 

 

 

 

 

 

 

restricted in 6/7 of the rated frequency.

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

DRY

COOL

Maximum frequency

 

 

5

 

 

 

 

 

 

 

 

 

1

1

8/10 of maximum frequency

 

 

6

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

 

 

 

 

 

 

 

 

 

4

7

40

120

101

58

40

120

100

108

 

1

2

9/10 of maximum frequency

 

 

8

 

 

 

 

 

 

 

 

 

1

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

2

1

7/10 of maximum frequency

 

 

10

 

 

 

 

 

 

 

 

 

3

1

 

 

 

 

 

 

 

 

 

 

 

 

 

22