• When the operation frequency does not go up from lowest frequency.
![](/images/new-backgrounds/1060917/6091765xi2.webp)
H Check of HPS
Start
1.Disconnect the connector CN722 in the electronic control P. C. board.
2.Check the resistance of HPS after 1 minutes have passed since the outdoor unit power supply was turnd off.
Check the resistance between | Infinity |
each terminal? | Replace HPS (63H1). |
| |
0" |
|
Return CN722 to former.
Turn on power supply to the indoor and outdoor unit. 3 minutes lator, EMERGENCY OPERATION starts.
Yes
Is HPS protection displayed
No
immediately after compressor Replace the electronic control P. C. board. starts.
Yes
Normal
![](/images/new-backgrounds/1060917/6091765xi4.webp)
I The other cases
In the case that the indoor fan and outdoor fan operate but the compressor does not operate, it causes that the high pressure switch can be operated once.
First of all, check the high pressure switch can be shorted, turn OFF the power and turn ON again 1 minute later. Indoor unit dose not operate. (difference modes)
•When you try to run two indoor unit simultaneously, one for cooling and the other for heating, the unit which transmits signal to the outdoor units earlier decides the operation mode. The other unit indicates as shown in the figure below.
•When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back ON.
•Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas continuously flows into the indoor unit even while it is not operating.