Mitsubishi Electronics MXZ-32SV service manual Check the contact of LEV board connec

Models: MXZ-32SV

1 44
Download 44 pages 62.89 Kb
Page 27
Image 27

Symptom

 

Outdoor unit operates. (The compressor operates at reduced frequency.)

 

 

 

 

Display

Detecting method

Detecting method

Check points

 

 

 

 

d8

Frequency drop by current

When the outdoor unit input current exceeds 22.5 A, the compressor

 

(d8)

protection

operates at reduced frequency.

 

d9

Frequency drop by overload

When the compressor load exceeds the specified value, the compres-

These symptoms do not mean any

(d9)

protection

sor operates at reduced frequency.

abnormality of the product, but check the

 

 

 

 

Frequency drop by high pres-

When indoor pipe temperature exceeds 55˚C during heating, the com-

following points.

d7

sure protection

pressor operates at reduced frequency.

• Air filter clogging.

(d7)

 

 

• Amount of gas.

Frequency drop by defrosting

When the indoor pipe temperature falls to 6˚C or below during cooling,

• Short cycle of indoor/outdoor air flow.

 

in cooling

the compressor operates at reduced frequency.

 

 

 

 

 

d6

Frequency drop by discharge

When the discharge temperature exceeds 110˚C, the compressor oper-

 

(d6)

temperature protection

ates at reduced frequency.

 

d3

Frequency drop by high pres-

When the high pressure exceeds 2.75MPa (28 kgf/cm2-G), the com-

• Amount of gas.

(d3)

sure switch protection

pressor operates at reduced frequency. In addition, the fan speed

• Outdoor unit air passage.

 

changes.

 

 

 

 

 

d1

 

When the state with low discharge temperature of which 50˚C in COOL

Check the amount of gas.

Low discharge temperature

• Replace the outdoor controller board.

(d1)

protection

and 48.4 or less in HEAT for 20 minutes, the compressor operates con-

• Check the contact of LEV board connec-

 

tinuously.

tors.

 

 

 

 

 

 

 

 

 

 

 

Symptom

 

Outdoor unit operates.

 

 

 

 

 

Display

Detecting method

Detecting method

Check points

 

 

 

 

e7

Defrost thermistor abnormality

When a short or open circuit occurs in the defrost thermistor during

• Defrost thermistor characteristic.

(E7)

heating

• Contact of P. C. board connectors.

 

* In this case, the compressor continues to operate.

 

 

 

 

 

 

h4

Power factor detection abnor-

When the compressor power factor cannot be detected

• Compressor wiring.

(h4)

mality

* In this case, the compressor keeps running.

 

 

 

 

 

 

 

 

27

Page 27
Image 27
Mitsubishi Electronics MXZ-32SV service manual Check the contact of LEV board connec