RX Torque Reference Setpoint #1

RX Torque Reference Setpoint #2

RX Torque Reference Setpoint #1

Program Frequency Settings Speed Reference Setpoints RX

Torque Reference Setpoint #1

This parameter is used to set the direction, gain, and bias of the RX input terminal when the RX terminal is used as the control input while operating in the Torque Control mode.

RX Input Torque Control Setup

Perform the following setup to allow the system to receive Torque control input at the RX input terminal:

Program Utilities

Command and Frequency Settings Command

 

Mode Select Terminal Block.

Program Utilities Command and Frequency Settings Frequency#1

 

Mode Select RX.

 

Provide a Run command (F and/or R).

Torque Control

Perform the following setup to allow the system to perform Torque control from the RX input terminal:

Set RX Torque Reference Setpoint #1,

Set the RXinput signal level (RXSpeed Ref #1) that represents theRX

 

Torque Reference Setpoint #1,

Set RX Torque Reference Setpoint #2, and

Set the RX input signal level (RX Speed Ref #2) that represents the RX

 

Torque Reference Setpoint #2.

This is accomplished by establishing an associated V/f output pattern for a given RX input level.

This parameter sets RX Torque Reference #1 and is the output torque value that is associated with the setting of RX Speed Reference #1 when operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

Torque Settings

RX Torque Reference Setpoint #2

Program Frequency Settings

Speed Reference Setpoints

RX

Torque Reference Setpoint #2

 

 

This parameter is used to set the direction, gain, and bias of the RX input terminal when the RX terminal is used as the control input while operating in the Torque Control mode.

This is accomplished by establishing an associated V/f output pattern for a given RX input level.

See RX Torque Reference Setpoint #1 for further information on this setting.

This parameter sets RX Torque Reference Setpoint #2 and is the output torque value that is associated with setting of RX Speed Reference Setpoint #2 when operating in the Torque control mode.

This value is entered as -250 to +250% of the rated torque.

118

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.0

Maximum — +250.0

Units — %

W7 ASD Installation and Operation Manual

Page 124
Image 124
Toshiba W7 manual RX Torque Reference Setpoint #1, RX Torque Reference Setpoint #2