Overcurrent Stall Level

 

 

Overtorque Trip

 

 

 

 

Overcurrent Stall Level

 

 

 

Program

Protection Settings

Overcurrent Stall Level

Parameter Type — Numerical

 

 

 

 

 

Factory Default — (ASD-dependent)

This parameter specifies the output current level at which the output frequency

 

is reduced in an attempt to prevent a trip. The overcurrent level is entered as a

Changeable During Run — Yes

percentage of the maximum rating of the ASD.

 

Note: Soft Stall must be enabled to use this feature.

Minimum — 0.00

Maximum — 200.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units — %

 

 

Overload Reduction Starting Frequency

 

Program

Protection Settings

Overload Reduction Starting

Parameter Type — Numerical

 

 

 

 

 

 

Frequency

 

 

 

 

 

Factory Default — 6.00

 

 

 

 

 

 

 

This parameter is used to reduce the start frequency during very low-speed

Changeable During Run — Yes

motor operation. During very low-speed operation the cooling efficiency of the

 

motor decreases. Lowering the start frequency aides in minimizing the

Minimum — 0.00

generated heat.

 

 

 

 

Maximum — 30.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units — Hz

 

 

Overspeed Detection Frequency Range

 

Program

Protection Settings

Overspeed Detection Frequency

Parameter Type — Numerical

Range

 

 

 

 

Factory Default — 0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

This parameter sets the upper level of the Base Frequency range that, once

Changeable During Run — Yes

exceeded, will cause an Overspeed Detected alert.

 

 

 

 

 

 

 

 

Minimum — 0.0

 

 

 

 

 

 

 

Maximum — 30.0

 

 

 

 

 

 

 

Units — Hz

 

 

 

Overtorque Detection Time

 

 

Program

 

Protection Settings

 

Overtorque Detection Time

Parameter Type — Numerical

This parameter sets the amount of time that the overtorque condition may

Factory Default — 0.50

 

exceed the tripping threshold level set at Overtorque Trip/Alarm Level

Changeable During Run — No

(Positive Torque) and Overtorque Trip/Alarm Level (Negative Torque)

 

before a trip occurs.

 

 

Minimum — 0.00

 

 

 

 

 

 

 

Maximum — 100.0

 

 

 

 

 

 

 

Units — Seconds

 

 

 

 

Overtorque Trip

 

 

 

Program

 

Protection Settings

 

Overtorque Trip

Parameter Type — Selection List

This parameter Enables/Disables the Over Torque Tripping function.

Factory Default — Disabled

 

When enabled, the ASD trips if an output torque larger than the setting of

Changeable During Run — No

parameters Overtorque Trip/Alarm Level (Positive Torque) or Overtorque

 

Trip/Alarm Level (Positive Torque) is detected for a time longer than the

 

setting of the Overtorque Detection Time parameter.

 

When disabled,

the ASD does not tripdue to overtorque conditions.

 

W7 ASD Installation

and Operation Manual

93

Page 99
Image 99
Toshiba W7 manual Overcurrent Stall Level, Overload Reduction Starting Frequency, Overspeed Detection Frequency Range