Overcurrent Stall Level |
|
| Overtorque Trip | |||||
|
|
|
| |||||
Overcurrent Stall Level |
|
|
| |||||
Program | ⇒ | Protection Settings | ⇒ | Overcurrent Stall Level | Parameter Type — Numerical | |||
|
|
|
|
| Factory Default — | |||
This parameter specifies the output current level at which the output frequency | ||||||||
| ||||||||
is reduced in an attempt to prevent a trip. The overcurrent level is entered as a | Changeable During Run — Yes | |||||||
percentage of the maximum rating of the ASD. | ||||||||
| ||||||||
Note: Soft Stall must be enabled to use this feature. | Minimum — 0.00 | |||||||
Maximum — 200.0 | ||||||||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Units — % | |
|
| |||||||
Overload Reduction Starting Frequency |
| |||||||
Program | ⇒ | Protection Settings | ⇒ | Overload Reduction Starting | Parameter Type — Numerical | |||
|
|
|
|
|
| |||
Frequency |
|
|
|
|
| Factory Default — 6.00 | ||
|
|
|
|
|
|
| ||
This parameter is used to reduce the start frequency during very | Changeable During Run — Yes | |||||||
motor operation. During very | ||||||||
| ||||||||
motor decreases. Lowering the start frequency aides in minimizing the | Minimum — 0.00 | |||||||
generated heat. |
|
|
|
| Maximum — 30.00 | |||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| Units — Hz | |
|
| |||||||
Overspeed Detection Frequency Range |
| |||||||
Program | ⇒ | Protection Settings | ⇒ | Overspeed Detection Frequency | Parameter Type — Numerical | |||
Range |
|
|
|
| Factory Default — 0.0 | |||
|
|
|
|
|
| |||
|
|
|
|
|
|
| ||
This parameter sets the upper level of the Base Frequency range that, once | Changeable During Run — Yes | |||||||
exceeded, will cause an Overspeed Detected alert. | ||||||||
| ||||||||
|
|
|
|
|
|
| Minimum — 0.0 | |
|
|
|
|
|
|
| Maximum — 30.0 | |
|
|
|
|
|
|
| Units — Hz | |
|
|
| ||||||
Overtorque Detection Time |
|
| ||||||
Program |
| Protection Settings |
| Overtorque Detection Time | Parameter Type — Numerical | |||
This parameter sets the amount of time that the overtorque condition may | Factory Default — 0.50 | |||||||
| ||||||||
exceed the tripping threshold level set at Overtorque Trip/Alarm Level | Changeable During Run — No | |||||||
(Positive Torque) and Overtorque Trip/Alarm Level (Negative Torque) | ||||||||
| ||||||||
before a trip occurs. |
|
| Minimum — 0.00 | |||||
|
|
|
|
|
|
| Maximum — 100.0 | |
|
|
|
|
|
|
| Units — Seconds | |
|
|
|
| |||||
Overtorque Trip |
|
|
| |||||
Program |
| Protection Settings |
| Overtorque Trip | Parameter Type — Selection List | |||
This parameter Enables/Disables the Over Torque Tripping function. | Factory Default — Disabled | |||||||
| ||||||||
When enabled, the ASD trips if an output torque larger than the setting of | Changeable During Run — No | |||||||
parameters Overtorque Trip/Alarm Level (Positive Torque) or Overtorque |
| |||||||
Trip/Alarm Level (Positive Torque) is detected for a time longer than the |
| |||||||
setting of the Overtorque Detection Time parameter. |
| |||||||
When disabled,⇒ | the ASD does not trip⇒due to overtorque conditions. |
| ||||||
W7 ASD Installation⇒ | and Operation Manual⇒ | 93 |