F Terminal Delay

 

 

 

 

Input Feedback Selection

 

 

 

 

 

 

F Terminal Delay

 

 

 

 

 

Program

Terminal Settings

 

Terminal Delays Input Terminal

Parameter Type — Numerical

Delays

 

 

⇒⇒

 

F

 

 

 

 

 

Factory Default — 8.0

This parameter delays the response of the ASD to any change in the F terminal

Changeable During Run — No

input by the programmed value.

 

 

 

 

The delay may be increased to provide additional electrical noise immunity or

Minimum — 2.0

to prevent the ASD from responding to contact bounce or chatter.

Maximum — 200.0

 

 

 

 

 

 

 

Units — mS

 

 

 

 

 

Hz Per User-defined Unit

 

 

 

 

Program

 

Utilities

Display Attributes Hz Per User Defined Unit

Parameter Type — Numerical

 

 

 

 

 

Factory Default — 0.00

This parameter allows the user to input a quantity to be displayed on the EOI

 

that is proportional to the output frequency of the drive.

Changeable During Run — Yes

 

 

 

 

 

 

 

This feature is useful when the output of a process is moved along at a rate that

Minimum — 0.00

is proportional to the output frequency of the drive.

 

 

 

 

 

 

 

 

Maximum — 200.0

 

 

 

 

 

 

 

Units — Hz/UDU

 

 

 

 

Input Feedback Selection

 

 

 

Program

Feedback Settings

Input Feedback Selection

Parameter Type — Selection List

 

 

 

 

 

Factory Default — PID Disabled

This parameter Enables/Disables PID feedback control. This parameter is

 

enabled by selecting a source for motor-control feedback.

Changeable During Run — Yes

 

 

 

 

 

 

 

Settings:

 

 

 

 

 

 

 

PID (Control) Disabled

 

 

 

 

VI/II

 

 

 

 

 

RR

 

 

 

 

 

RX

 

 

 

 

 

RX2 (option)

 

 

 

76

W7 ASD Installation and Operation Manual

Page 82
Image 82
Toshiba W7 Hz Per User-defined Unit, Input Feedback Selection, Terminal Delay, Display Attributes Hz Per User Defined Unit