Toshiba W7 manual RS232/RS485 Baud Rate, RS232/RS485 Communication Time-Out Action

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 116
Image 116

RS232/RS485 Baud Rate

 

RS232/RS485 Communication Time-Out Time

 

 

 

 

RS232/RS485 Baud Rate

 

 

 

Program

Communication Settings

RS232/RS485 Baud Rate

Parameter Type — Selection List

This parameter sets the RS232/RS485 baud rate.

Factory Default — 9600

 

Changes made to this parameter require that the power be cycled (Off then On)

Changeable During Run — Yes

for the changes to take effect.

 

 

 

Settings:

 

 

 

 

1200

 

 

 

 

2400

 

 

 

 

4800

 

 

 

 

9600

 

 

 

 

19200

 

 

 

 

38400

 

 

 

 

 

 

RS232/RS485 Communication Time-Out Action

 

Program

Communication Settings

RS232/RS485 Timeout Action

Parameter Type — Selection List

This parameter plays a role in the setup of the communications network by

Factory Default — 485-Alarm – TTL-

None

determining the action to be taken in the event of a time-out (Time-Out

 

Action).

 

 

 

Changeable During Run — Yes

 

 

 

 

The communications network includes other ASDs and Host/Control computers

 

that monitorthe status of the ASD(s), transfers

commands, and loads or

 

modifies theparameter settings of the ASD.

 

 

 

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Settings:

None

RS232/RS485-AlarmTTL-None

RS232/RS485-TripTTL-None

RS232/RS485-NoneTTL-Alarm

RS232/RS485-AlarmTTL-Alarm

RS232/RS485-TripTTL-Alarm

RS232/RS485-NoneTTL-Trip

RS232/RS485-AlarmTTL-Trip

RS232/RS485-TripTTL-Trip

RS232/RS485 Communication Time-Out Time

Program

Communication Settings

485 Timeout Time

110

This parameter plays a role in the setup of the communications network by setting the time that no activity may exist over the communications link before the link is severed (Time Out).

The communications network includes other ASDs and Host/Control computers that monitor the status of the ASD(s), transfers commands, and loads or modifies the parameter settings of the ASD.

Changes made to this parameter require that the power be cycled (Off then On) for the changes to take effect.

Parameter Type — Numerical

Factory Default — 0

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — Seconds

W7 ASD Installation and Operation Manual

Page 116