Toshiba W7 Panel Stop Pattern, Panel V/f Group Selection, Parity RS232/RS485/TTL, PG Input Phases

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 102
Image 102

Panel Stop Pattern

 

PG Input Phases

 

 

 

Panel Stop Pattern

 

 

Program

Panel Control Panel Stop Pattern

Parameter Type — Selection List

The Decel Stop or Coast Stop settings determine the method used to stop the

Factory Default — Decel Stop

 

motor when using the StopReset key of the keypad.

Changeable During Run — Yes

 

 

 

 

The Decel Stop setting enables either the Dynamic Braking system or the DC

 

Injection Braking system. The Coast Stop setting allows the motor to stop at

 

the rate allowed by the inertia of the load.

 

 

 

 

Panel V/f Group Selection

 

 

Program

Panel Control Panel V/f Group Selection

Parameter Type — Selection List

This parameter is used to select 1 of 4 V/f profiles may be selected and run.

Factory Default — 1

 

Each V/f profile is comprised of 4 user settings: Base Frequency, Base

Changeable During Run — Yes

Frequency Voltage, Manual Torque Boost, and Thermal Protection.

 

Settings:

 

 

 

 

1

 

 

 

 

2

 

 

 

 

3

 

 

 

 

4

 

 

 

 

⇒⇒

 

 

Parity (RS232/RS485/TTL)

 

 

Program

Communication Settings Parity (RS232/RS485/TTL)

Parameter Type — Selection List

This parameter plays a role in the setup of the communications network by

Factory Default — Even Parity

 

establishing the Parity setting of the communications link.

Changeable During Run — Yes

 

 

 

 

The communications network includes other ASDs and Host/Control computers

 

that monitor the status of the ASD(s), transfers commands, and loads or

 

modifies the parameter settings of the ASD.

 

Changes made to this parameter require that the power be cycled (Off then On)

 

for the changes

to take effect.

 

 

Settings:

 

 

 

 

No Parity

 

 

 

 

Even Parity

 

 

 

Odd Parity

 

 

 

 

 

PG Disconnect Detection Selection

 

Program

Feedback Settings

PG Disconnect Detection Selection

Parameter Type — Selection List

This parameter Enables/Disables the system’s monitoring of the PG connection

Factory Default — Disabled

 

status when using encoders with line driver outputs.

Changeable During Run — Yes

 

PG Input Phases

 

 

Program Feedback Settings PG Input Phases

This setting determines if motor speed and direction will be conveyed by the encoder.

Settings:

Single-Phase

Two-Phase

Parameter Type — Selection List

Factory Default — Two-Phase

Changeable During Run — No

96

W7 ASD Installation and Operation Manual

Page 102
Image 102
Toshiba W7 manual Panel Stop Pattern, Panel V/f Group Selection, Parity RS232/RS485/TTL, PG Disconnect Detection Selection