Panel Stop Pattern |
| PG Input Phases | |||
|
|
| |||
Panel Stop Pattern |
|
| |||
Program | Panel Control Panel Stop Pattern | Parameter Type — Selection List | |||
The Decel Stop or Coast Stop settings determine the method used to stop the | Factory Default — Decel Stop | ||||
| |||||
motor when using the StopReset key of the keypad. | Changeable During Run — Yes | ||||
|
|
|
| ||
The Decel Stop setting enables either the Dynamic Braking system or the DC |
| ||||
Injection Braking system. The Coast Stop setting allows the motor to stop at |
| ||||
the rate allowed by the inertia of the load. |
| ||||
|
|
| |||
Panel V/f Group Selection |
|
| |||
Program | Panel Control Panel V/f Group Selection | Parameter Type — Selection List | |||
This parameter is used to select 1 of 4 V/f profiles may be selected and run. | Factory Default — 1 | ||||
| |||||
Each V/f profile is comprised of 4 user settings: Base Frequency, Base | Changeable During Run — Yes | ||||
Frequency Voltage, Manual Torque Boost, and Thermal Protection. | |||||
| |||||
Settings: |
|
|
|
| |
1 |
|
|
|
| |
2 |
|
|
|
| |
3 |
|
|
|
| |
4 |
|
|
|
| |
⇒⇒ |
|
| |||
Parity (RS232/RS485/TTL) |
|
| |||
Program | Communication Settings Parity (RS232/RS485/TTL) | Parameter Type — Selection List | |||
This parameter plays a role in the setup of the communications network by | Factory Default — Even Parity | ||||
| |||||
establishing the Parity setting of the communications link. | Changeable During Run — Yes | ||||
|
|
|
| ||
The communications network includes other ASDs and Host/Control computers |
| ||||
that monitor the status of the ASD(s), transfers commands, and loads or |
| ||||
modifies the parameter settings of the ASD. |
| ||||
Changes made to this parameter require that the power be cycled (Off then On) |
| ||||
for the changes⇒ | to take effect.⇒ |
|
| ||
Settings: |
|
|
|
| |
No Parity |
|
|
|
| |
Even Parity |
|
|
| ||
Odd Parity |
|
|
| ||
|
| ||||
PG Disconnect Detection Selection |
| ||||
Program | Feedback Settings | PG Disconnect Detection Selection | Parameter Type — Selection List | ||
This parameter Enables/Disables the system’s monitoring of the PG connection | Factory Default — Disabled | ||||
| |||||
status when using encoders with line driver outputs. | Changeable During Run — Yes | ||||
⇒ | ⇒ | ||||
| |||||
PG Input Phases |
|
|
Program ⇒Feedback Settings ⇒PG Input Phases
This setting determines if motor speed and direction will be conveyed by the encoder.
Settings:
Parameter Type — Selection List
Factory Default —
Changeable During Run — No
96 | W7 ASD Installation and Operation Manual |