OUT1 On Delay |
|
|
|
|
|
| OUT2 Terminal | ||||
|
|
|
|
|
|
| |||||
OUT1 On Delay |
|
|
|
|
|
| |||||
Program | ⇒ | Terminal Settings | ⇒ | Terminal Delays | ⇒ | Output Terminal | Parameter Type — Numerical | ||||
Delays |
|
|
|
|
| ||||||
| OUT1 | OUT1 On Delay |
|
|
| Factory Default — 2.0 | |||||
|
|
|
|
|
|
|
|
|
| ||
Once the condition is met to change the state of the OUT1 (A & C) output | Changeable During Run — No | ||||||||||
contacts, this parameter delays the response of the contacts by the programmed | |||||||||||
| |||||||||||
value (see waveforms at FL On Delay). |
|
|
| Minimum — 2.0 | |||||||
The delay may be increased to prevent relay chatter. |
|
|
| Maximum — 200.0 | |||||||
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| Units — mS | |
|
|
|
|
|
|
| |||||
OUT1 Terminal |
|
|
|
|
|
| |||||
Program | ⇒ | Terminal Settings | ⇒ | Output Terminals |
| OUT1 Terminal | Parameter Type — Selection List | ||||
|
|
|
|
| ⇒ |
| |||||
Assignment |
|
|
|
|
|
| Factory Default — Damper Cmd | ||||
This parameter sets the functionality of the OUT1 (A & C) output contacts to 1 | Changeable During Run — No | ||||||||||
of the 58 possible functions that are listed in Table 7 on page 141. |
| ||||||||||
The on and off delay times of the OUT1 contacts may be adjusted to provide |
| ||||||||||
more response time to the device that is connected to the output terminals. |
| ||||||||||
In addition, the output contacts must be specified as Normally Open or |
| ||||||||||
Normally Closed. |
|
|
|
|
|
|
| ||||
OUT2 Off Delay |
|
|
|
|
|
| |||||
Program⇒⇒Terminal Settings |
| Terminal Delays |
|
| Output Terminal | Parameter Type — Numerical | |||||
Delays | ⇒ |
|
| ⇒⇒ |
|
| |||||
| OUT2 Off Delay |
|
|
|
|
| Factory Default — 2.0 | ||||
Once the condition is met to change the state of the OUT2 (A & C) output | Changeable During Run — No | ||||||||||
contacts, this parameter delays the response of the contacts by the programmed |
| ||||||||||
value (see waveforms at FL Off Delay). |
|
|
| Minimum — 2.0 | |||||||
The on and off delay times of the OUT2 contacts may be adjusted to provide | Maximum — 200.0 | ||||||||||
more response time to the device that is connected to the output terminals. |
| ||||||||||
|
|
|
|
|
|
|
|
|
| Units — mS | |
OUT2 On Delay |
|
|
|
|
|
| |||||
Program | ⇒ | Terminal Settings |
| Terminal Delays |
|
| Output Terminal | Parameter Type — Numerical | |||
Delays |
|
| ⇒⇒ |
|
| ||||||
| OUT2 On Delay |
|
|
|
|
| Factory Default — 2.0 | ||||
⇒ |
|
|
|
|
|
|
|
| |||
This parameter delays the response of the OUT2 (A & C) output contacts by | Changeable During Run — No | ||||||||||
the programmed value (see waveforms at FL On Delay). |
|
| |||||||||
The delay may be increased to prevent relay chatter. |
|
|
| Minimum — 2.0 | |||||||
|
|
|
|
|
|
|
|
|
| Maximum — 200.0 | |
|
|
|
|
|
|
|
|
|
| Units — mS | |
OUT2 Terminal |
|
|
|
|
|
| |||||
Program⇒ |
| Terminal Settings |
| Output Terminals |
| OUT2 Terminal | Parameter Type — Selection List | ||||
Assignment |
|
|
|
|
|
| Factory Default — Acc/Dec Completion | ||||
|
|
|
|
|
|
|
|
|
| ||
This parameter sets the functionality of the OUT2 (A & C) output contacts to 1 | Changeable During Run — No | ||||||||||
of the 58 possible functions that are listed in Table 7 on page 141. | |||||||||||
| |||||||||||
The on and off delay times of the OUT2 contacts may be adjusted to provide |
| ||||||||||
more response time to the device that is connected to the output terminals. |
| ||||||||||
In addition, the output contacts must be specified as Normally Open or |
| ||||||||||
Normally Closed. | and Operation⇒Manual |
| ⇒ |
| |||||||
W7 ASD Installation⇒ |
| 89 |