Toshiba W7 manual OUT1 On Delay, OUT1 Terminal, OUT2 Off Delay, OUT2 On Delay, OUT2 Terminal

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 95
Image 95

OUT1 On Delay

 

 

 

 

 

 

OUT2 Terminal

 

 

 

 

 

 

 

OUT1 On Delay

 

 

 

 

 

 

Program

Terminal Settings

Terminal Delays

Output Terminal

Parameter Type — Numerical

Delays

 

 

 

 

 

 

OUT1

OUT1 On Delay

 

 

 

Factory Default — 2.0

 

 

 

 

 

 

 

 

 

 

Once the condition is met to change the state of the OUT1 (A & C) output

Changeable During Run — No

contacts, this parameter delays the response of the contacts by the programmed

 

value (see waveforms at FL On Delay).

 

 

 

Minimum — 2.0

The delay may be increased to prevent relay chatter.

 

 

 

Maximum — 200.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units — mS

 

 

 

 

 

 

 

OUT1 Terminal

 

 

 

 

 

 

Program

Terminal Settings

Output Terminals

 

OUT1 Terminal

Parameter Type — Selection List

 

 

 

 

 

 

Assignment

 

 

 

 

 

 

Factory Default — Damper Cmd

This parameter sets the functionality of the OUT1 (A & C) output contacts to 1

Changeable During Run — No

of the 58 possible functions that are listed in Table 7 on page 141.

 

The on and off delay times of the OUT1 contacts may be adjusted to provide

 

more response time to the device that is connected to the output terminals.

 

In addition, the output contacts must be specified as Normally Open or

 

Normally Closed.

 

 

 

 

 

 

 

OUT2 Off Delay

 

 

 

 

 

 

Program⇒⇒Terminal Settings

 

Terminal Delays

 

 

Output Terminal

Parameter Type — Numerical

Delays

 

 

⇒⇒

 

 

 

OUT2 Off Delay

 

 

 

 

 

Factory Default — 2.0

Once the condition is met to change the state of the OUT2 (A & C) output

Changeable During Run — No

contacts, this parameter delays the response of the contacts by the programmed

 

value (see waveforms at FL Off Delay).

 

 

 

Minimum — 2.0

The on and off delay times of the OUT2 contacts may be adjusted to provide

Maximum — 200.0

more response time to the device that is connected to the output terminals.

 

 

 

 

 

 

 

 

 

 

 

Units — mS

OUT2 On Delay

 

 

 

 

 

 

Program

Terminal Settings

 

Terminal Delays

 

 

Output Terminal

Parameter Type — Numerical

Delays

 

 

⇒⇒

 

 

 

OUT2 On Delay

 

 

 

 

 

Factory Default — 2.0

 

 

 

 

 

 

 

 

This parameter delays the response of the OUT2 (A & C) output contacts by

Changeable During Run — No

the programmed value (see waveforms at FL On Delay).

 

 

The delay may be increased to prevent relay chatter.

 

 

 

Minimum — 2.0

 

 

 

 

 

 

 

 

 

 

Maximum — 200.0

 

 

 

 

 

 

 

 

 

 

Units — mS

OUT2 Terminal

 

 

 

 

 

 

Program

 

Terminal Settings

 

Output Terminals

 

OUT2 Terminal

Parameter Type — Selection List

Assignment

 

 

 

 

 

 

Factory Default — Acc/Dec Completion

 

 

 

 

 

 

 

 

 

 

This parameter sets the functionality of the OUT2 (A & C) output contacts to 1

Changeable During Run — No

of the 58 possible functions that are listed in Table 7 on page 141.

 

The on and off delay times of the OUT2 contacts may be adjusted to provide

 

more response time to the device that is connected to the output terminals.

 

In addition, the output contacts must be specified as Normally Open or

 

Normally Closed.

and OperationManual

 

 

W7 ASD Installation

 

89

Page 95
Image 95
Toshiba W7 manual OUT1 On Delay, OUT1 Terminal, OUT2 Off Delay, OUT2 On Delay, OUT2 Terminal