Communications Frequency Setpoint #1

 

 

CPU Version

 

 

Communications Frequency Setpoint #1

 

Program

 

Communications Settings

 

Communications Speed

Parameter Type — Numerical

Setpoint #1

 

 

 

 

 

 

Factory Default — 0.00

 

 

 

 

 

 

 

 

 

This parameter is used to set the gain and bias of the Communications

Changeable During Run — Yes

Reference speed control input.

 

 

 

 

 

 

 

 

 

See Communications Reference Setpoint #1 for further information on this

Minimum — 0.00

 

setting.

 

 

 

 

 

 

 

 

Maximum — Max. Freq.

 

 

 

 

 

 

 

 

 

This parameter sets Communications Speed #1.

Units — Hz

Changes made to this parameter require that the power be cycled (Off then On)

 

for the changes to take effect.

 

 

 

 

 

 

 

 

Communications Frequency Setpoint #2

 

Program

Communications Settings

 

Communications Speed

Parameter Type — Numerical

 

 

 

 

 

 

 

Setpoint #2

 

 

 

 

 

 

Factory Default — 80.0

This parameter is used to set the gain and bias of the Communications

Changeable During Run — Yes

Reference speed control input.

 

 

 

 

 

See Communications Reference Setpoint #1 for further information on this

Minimum — 0.0

setting.

 

 

 

 

 

 

 

 

Maximum — Max. Freq.

This parameter sets the Communications Speed #2.

Units — Hz

Changes madeto this parameter require thatthe power be cycled (Off then On)

 

for the changes to take effect.

 

 

 

 

 

 

Cooling Fan Control

 

 

 

 

 

 

Program

Protection Settings

Cooling Fan Control

Parameter Type — Selection List

 

 

 

 

 

 

 

Factory Default — Automatic

This parameter sets the cooling fan run-time command.

 

Settings:

 

 

 

 

 

 

 

 

Changeable During Run — Yes

 

 

 

 

 

 

 

 

 

Automatic

 

 

 

 

 

 

 

 

Always On

 

 

 

 

 

 

 

 

 

 

 

 

 

Continuing Stall Period

 

 

 

 

 

Program

 

Protection Settings Continuing Stall Period

Parameter Type — Numerical

This setting allows the user to extend the Overvoltage Stall and the

Factory Default — 0.00

 

Overcurrent Stall time settings.

 

 

 

 

Changeable During Run — No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum — 0.00

 

 

 

 

 

 

 

 

 

Maximum — 1.00

 

 

 

 

 

 

 

 

 

Units — Seconds

 

 

 

 

 

 

 

 

CPU Revision

 

 

 

 

 

 

 

Program

 

Utilities

Version

CPU Revision Level

 

This is a read-only parameter that displays the revision level of the CPU.

 

 

 

 

 

 

 

 

 

CPU Version

 

 

 

 

 

 

 

Program

 

Utilities

Version

CPU Revision Level

 

64This is a read-only parameter

that displays

the version level of the CPU.

W7 ASD Installation and Operation Manual

Page 70
Image 70