Toshiba W7 manual Dynamic Braking Enable, Dynamic Braking Resistance

Models: W7

1 167
Download 167 pages 14.06 Kb
Page 74
Image 74

Dynamic Braking Enable

Dynamic Braking Resistance Capacity

Dynamic Braking Enable

Program Protection Settings Dynamic Braking Enable

This parameterEnables/Disables theDynamic Braking system.

Settings:

Enabled

Disabled

Dynamic Braking

Dynamic Braking uses the inertial energy of the load to produce a braking force or it may be used to reduce the bus voltage in an attempt to preclude an overvoltage trip during deceleration. The inertial energy of the load drives the rotor and induces a current into the stator of the motor.

The induced stator current (energy) is dissipated through a resistive load. The resistive load is connected across terminals PA and PB (non-polarized). Using a low-value, high-wattage resistance as a load for the generated current, the resistive load dissipates the induced energy. The dissipated energy is the energy that would otherwise have caused the rotor to continue to rotate.

Dynamic Braking helps to slow the load quickly; it cannot act as a holding brake.

The Dynamic Braking function may be setup and enabled by connecting a braking resistor from terminal PA to PB of the ASD and providing the proper information at the DBR parameters: Dynamic Braking Resistor (DBR)

Capacity, Dynamic Braking Resistance, and DC Injection Braking Current.

For additional information on selecting the proper resistance value for a given application contact Toshiba’s Marketing Department.

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Dynamic Braking Resistance

Program

Protection Settings

Dynamic Braking Resistance

Parameter Type — Numerical

 

 

 

Factory Default — (ASD-dependent)

This parameter is used to input the resistive value of the Dynamic Braking

 

Resistor.

 

 

 

 

Changeable During Run — No

 

 

 

 

 

Note: Using a resistor value that is too low may result in system

Minimum — 1.0

damage.

 

 

Maximum — 1000.0

 

 

 

 

 

 

 

 

 

 

Units —

 

 

Dynamic Braking Resistance Capacity

 

Program

 

Protection Settings

 

Dynamic Braking Resistance

Parameter Type — Numerical

Capacity

 

 

 

Factory Default — (ASD-dependent)

 

 

 

 

 

This parameter is used to input the wattage of the Dynamic Braking Resistor.

Changeable During Run — No

 

 

 

 

 

For additional information on selecting the proper resistor wattage value for a

Minimum — 0.01

given application contact Toshiba’s Marketing Department.

 

Note: Using a resistor with a wattage rating that is too low may

Maximum — 600.0

 

result in system damage.

 

Units — kW

68

 

 

W7 ASD Installation and Operation Manual

Page 74
Image 74
Toshiba W7 manual Dynamic Braking Enable, Dynamic Braking Resistance Capacity